How to Choose the Right IEC 61111:2009 Class for Rubber Insulating Mats
How to Choose the Right IEC 61111:2009 Class for Rubber Insulating Mats
How to Choose the Right IEC 61111:2009 Class for Electrical Insulating Rubber Mats
1.
Determine Your Maximum System Voltage
Start by identifying the highest voltage present in the work area.
Measure the nominal voltage of live parts (transformers, switchgear, cables).
Consider any temporary overvoltage or surge potentials (lightning, switching transients).
2.
Apply a Safety Margin
IEC 61111 voltage classes are discrete steps. To prevent breakdown under unexpected conditions:
Pick the next higher class above your system’s maximum voltage.
For example, if your highest live voltage is 11 kV, choose Class 3 (26.5 kV working voltage).
3.
Match to IEC 61111 Class Table
Once you know your system voltage plus margin, use this reference:
IEC 61111:2009 Class
Test Voltage
Working Voltage
Dielectric Strength
0
5 kV
1 000 V
10 kV
1
10 kV
7 500 V
20 kV
2
20 kV
17 000 V
30 kV
3
30 kV
26 500 V
40 kV
4
40 kV
36 000 V
50 kV
4.
Account for Environmental and Operational Factors
Beyond voltage, consider how, where, and how often the mats will be used:
Contamination risk (oil, dust, moisture): choose mats with higher slip-resistance grades.
Mechanical stress (foot traffic, tool drops): thicker mats offer greater durability.
Outdoor vs indoor: UV-resistant finishes matter if mats see sunlight.
5.
Validate with Risk Assessment
Perform or review a formal risk assessment to confirm:
All live-working tasks and their voltages are catalogued.
Possible overvoltage scenarios are covered by the selected class.
Environmental hazards will not undermine insulation integrity.
6.
Implement and Maintain
Mark or tag mats with their IEC 61111 class so users can verify compatibility at glance.
Train personnel to match mats to specific jobs and voltages.
Inspect, clean and retest mats per the standard’s intervals to ensure ongoing protection.