CVM-C4 Power Analyzer

CVM-C4 Power Analyzer

Danh mục: Circutor Có sẵn
Để biết thêm thông tin, truy cập trang web chính thức của chúng tôi tại saturnpyro.com

Mô tả

Circutor CVM-C4 Power Analyzer

Product model: CVM-C4-ITF-485-ICT2 | Code: M52706

Introduction

The Circutor CVM-C4 is a compact 96 x 96 mm panel-mounted power analyzer for single-phase and three-phase electrical networks. It measures, calculates and displays key electrical parameters using true RMS measurement, with indirect current measurement through /5 A or /1 A current transformers.

Positioning Statement

A compact multifunction panel analyzer for sites that need essential electrical measurement, energy logging, RS-485 Modbus communication and local alarm outputs in a space-saving installation depth.

Key Webpage Highlights

Product Description

The CVM-C4 is a multifunction power analyzer designed for electrical panels where space is limited but essential measurement and communication capability is required. The analyzer measures, calculates and displays the main electrical parameters of single-phase and three-phase installations, including networks with or without neutral. It supports true RMS measurement through three voltage inputs and three current inputs, with current measurement carried out through /5 A or /1 A external current transformers.
With RS-485 Modbus RTU communication, the CVM-C4 can be integrated into SCADA, EMS, BMS or other master systems for remote data readout and centralised monitoring. The relay outputs enable local operation when alarm conditions occur, while the digital inputs and impulse outputs support tariff/source metering and energy pulse applications.

Typical Applications

Application Area How CVM-C4 Helps
Compact electrical panels Suitable for panels with limited installation depth or limited front panel space.
Electrical parameter monitoring Displays instantaneous values of key electrical parameters locally on the LCD screen.
SCADA / EMS integration RS-485 Modbus RTU enables remote data collection and centralised monitoring.
Energy metering Logs consumed or generated active and reactive energy.
Alarm and local control Relay outputs can be programmed to activate based on alarm conditions.
Tariff or source separation Digital inputs can be used to measure energy from two different sources or tariffs.
Harmonic visibility Voltage and current THD% measurements help check harmonic presence in the installation.
 

Feature Table

Feature Datasheet Detail Webpage Value
Panel mounting 96 x 96 mm, 41.5 mm depth Compact installation for low-voltage panels and retrofit applications.
Network support Single-phase and three-phase networks, with or without neutral Flexible use across common electrical distribution configurations.
Measurement method True RMS measurement More reliable reading under non-ideal electrical conditions.
Current input .../5 A | .../1 A Works with standard external CT ratios.
Voltage input 3 AC voltage inputs Measures the main voltage parameters for three-phase systems.
Communication RS-485, Modbus RTU Suitable for SCADA, EMS, BMS and remote monitoring systems.
Relay outputs 2 relay outputs Supports local alarm or control actions.
Digital inputs 2 potential-free digital inputs Useful for source/tariff selection and dual energy metering.
Transistor outputs 2 passive impulse outputs Supports energy pulse output applications.
Harmonic check Voltage and current THD% Basic harmonic visibility for installation health checks.
 

Product Identification

Parameter Value
Product family CVM-C4
Model CVM-C4-ITF-485-ICT2
Code M52706
Product type Power analyzer / multifunctional multimeter for panel
Mounting Panel
Protocol Modbus RTU
Communication RS-485
Measuring current channels 3
Input current .../5 A | .../1 A
Transistor outputs 2
Relay outputs 2
Digital inputs 2
 

Power Supply

Parameter Value
AC nominal voltage 80 ... 270 Vac
AC frequency 50/60 Hz
AC consumption 6 ... 18 VA
AC installation category CAT III 300 V
DC nominal voltage 80 ... 270 Vdc
DC consumption 1.5 ... 1.8 W
DC installation category CAT III 300 V
 

Mechanical and Environmental

Parameter Value
Dimensions 96 x 96 x 41.5 mm
Envelope Polycarbonate + ABS
Torque setting 0.5 Nm
Terminal cable gauge 2.5 mm2
Weight 0.268 kg
Protection class Front: IP54, Rear: IP20
Relative humidity 5 ... 95%, without condensation
Storage temperature -20 ... +70 °C
Operating temperature -10 ... +60 °C
 

Current Measurement Circuit

Parameter Value
Installation category CAT III 300 V
Nominal current 1 A / 5 A AC
Consumption < 0.2 VA per phase
Allowable overload 1.2 In continuous, 10 In instantaneous for 5 s
 

Voltage Measurement Circuit

Parameter Value
Installation category CAT III 300 V
Nominal voltage 100 ... 277 V Ph-N, ±8%
Sampling / frequency range 45 ... 65 Hz
Input impedance > 1.7 MΩ
Consumption < 0.2 VA per phase
Maximum permanent measurement voltage 1.2 Un continuous, 2 Un instantaneous
 

Communication

Parameter Value
Protocol Modbus RTU
Interface RS-485
Speed 2400 / 4800 / 9600 / 19200 bps
Data bits 8
Stop bits 1-2
Parity None / Even / Odd
 

User Interface and I/O

Parameter Value
Display type LCD
Keyboard 3 keys
Digital inputs 2 potential-free contacts
Digital input insulation 3.75 kV RMS
Maximum short-circuit current 4 mA
Maximum open circuit voltage 30 V
Relay outputs 2 relay outputs
Relay resistive load 250 Vac / 5 Aac, 30 Vdc / 5 Adc
Relay maximum switching capacity 1385 VA / 150 W
Transistor output type Passive impulse
Transistor maximum frequency 10 Hz
Transistor maximum current 27 mA
Transistor maximum voltage 27 Vdc
 

Measurement Accuracy

Parameter Value
Frequency 0.5%
Phase current 0.2%
Phase voltage 0.2%
Active power 0.5%
Reactive power 0.5%
Active energy 0.5%
Reactive energy 0.5%
 

Standards

Parameter Value
Electrical safety maximum height 2000 m
Electrical safety installation category CAT III 300 V
Contamination level / class Pollution resistance 2
Standards IEC 61010-1, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11
 

Model / Ordering Table

Code Type Input Current Transistor Output No. Relays Digital Inputs Communication Protocol
M52706 CVM-C4-ITF-485-ICT2 .../5 A | .../1 A 2 2 2 RS-485 Modbus RTU

Additional note: 4-quadrant measuring unit. Can be used to program the voltage transformer ratio.

Product image 

Dimensions and connection overview 

Dimensions

Connection diagram


 

Xem thêm chi tiết về Saturn Pyro Sdn Bhd
Saturn Pyro Sdn Bhd
Saturn Pyro Sdn Bhd Energy Meters Supplier Johor Bahru (JB), Energy Management Malaysia, Selangor, Power Quality Analyzers Supply Kuala Lumpur (KL), Penang ~ Saturn Pyro Sdn Bhd