In the clinical landscape of 2026, Negative Pressure Isolation Room AHUs are the primary mechanical defense against the transmission of airborne pathogens. These systems are specifically engineered to keep infectious agents inside the patient room, preventing cross-contamination to corridors, nurse stations, and other wards.
At EKG (Malaysia) SDN BHD, we design these units to meet the stringent "Infectious Isolation" standards of MOH (Ministry of Health) Malaysia and ASHRAE 170, while ensuring compliance with the EECA 2024 energy efficiency mandates.
The goal of a negative pressure AHU is to create a "Vacuum Effect." This is achieved by ensuring that the volume of air exhausted from the room is significantly greater than the volume of air supplied ($Air_{out} > Air_{in}$).
Pressure Gradient: We typically maintain a differential of -15 Pa relative to the adjacent anteroom or corridor.
Inward Airflow: This gradient ensures that whenever a door is opened, air flows into the isolation room from the "clean" corridor, never the other way around.
Air Change Rates (ACH): To comply with clinical safety standards, these units provide a minimum of 12 Air Changes per Hour, rapidly diluting the concentration of airborne pathogens.
Isolation room AHUs require a unique internal architecture to handle potentially infectious air streams safely.
100% Fresh Air (Once-Through): To prevent any risk of recirculating pathogens, these systems typically operate on a "Once-Through" basis. All supply air is fresh, and 100% of the room air is exhausted and filtered.
Bag-In / Bag-Out (BIBO) Filtration: The exhaust stream is fitted with BIBO HEPA Filter Housings. This allows maintenance teams to replace contaminated H14 HEPA filters within a sealed PVC bag, ensuring they never come into direct contact with infectious material.
L1-Class Airtight Casing: In a negative pressure system, casing integrity is critical. Any leakage into the unit from the plant room would disrupt the precise pressure balance. Our L1-rated construction ensures a perfect seal.
| Feature | Standard Hospital AHU | EKG Isolation Room AHU |
| Air Strategy | Recirculated (80/20) | 100% Fresh Air (Once-Through) |
| Pressure Target | Neutral / Positive | Strict Negative (-15 Pa) |
| Exhaust Treatment | Standard | HEPA H14 + BIBO Housing |
| Airflow Control | Temperature Based | Active Airflow Tracking (VAV) |
| Sanitization | UV-C on Coils | UV-C + High-Intensity Exhaust UV |
| Energy Strategy | Basic | Run-Around Heat Recovery (EECA 2024) |
Running 100% fresh air in Malaysia’s tropical heat is energy-intensive. EKG utilizes specialized infrastructure to maintain a Low BEI (Building Energy Intensity):
Run-Around Coil Loops: Because supply and exhaust air must never mix, we use a liquid-coupled loop. This recovers "coolth" from the exhaust air to pre-cool incoming fresh air, saving up to 25% on chiller load without any risk of cross-contamination.
IE5 EC Fan Arrays: We utilize modular fan walls that provide the high static pressure required for HEPA filters while maintaining a Specific Fan Power (SFP) below 1.1 $kW/m^3/s$.
N+1 Redundancy: If a single fan in the array fails, the others automatically ramp up to ensure the room never loses its negative pressure protection.
Negative pressure is a life-safety metric that must be monitored 24/7.
Pressure Monitoring Panels: Every EKG installation includes medical-grade digital sensors at the door. If the pressure drops below the setpoint, local and central alarms are triggered immediately.
TB2 Thermal Break Casing: Prevents external "sweating." In a negative pressure plant room, moisture on the unit can lead to mold, which is a major violation of JKKP/DOSH and MOH clinical audits.
EnMS Integration: All data is logged to your Energy Management System (EnMS) for the Energy Commission's statutory audits.
Technical Integrity: We provide the full Validation Documentation (IQ/OQ) and Aerosol Mapping Reports required for clinical accreditation.
Precision BIM Coordination: We model the complex interaction between supply, exhaust, and BIBO filtration to ensure a clash-free installation in high-density hospital voids.
BOMBA-Compliant Safety: All internal materials and seals are fire-rated (Class 0 or B1).
Is your facility's isolation capacity meeting the 2026 safety and energy standards? Contact EKG (Malaysia) SDN BHD today. We specialize in engineering isolation systems that are silent, sterile, and ultra-efficient.