SIMATIC ET 200MP PROFINET IO device Interface module IM 155-5 PN BA for ET 200MP electronic modules; up to 12 IO modules; Integrated 2-port switch; RJ45 Shared Device with 2 IO controllers, MRP; FW update; I&M0...3

SIMATIC ET 200MP PROFINET IO device Interface module IM 155-5 PN BA for ET 200MP electronic modules; up to 12 IO modules; Integrated 2-port switch; RJ45 Shared Device with 2 IO controllers, MRP; FW update; I&M0...3

Danh mục: SIEMENS Simatic Control Systems Có sẵn
Để biết thêm thông tin, truy cập trang web chính thức của chúng tôi tại geasb.com

Mô tả

General information
Product type designation IM 155-5 PN BA
HW functional status From FS02
Firmware version V4.3.0
● FW update possible Yes
Vendor identification (VendorID) 0x002A
Device identifier (DeviceID) 0X0312
Product function
● I&M data Yes; I&M0 to I&M3
● Module swapping during operation (hot swapping) No
● Isochronous mode No
● IRT No
● Tool changer No
● Local coupling, IO data No
Engineering with
● STEP 7 TIA Portal configurable/integrated from version V15.1
● STEP 7 configurable/integrated from version use GSD file
● PROFINET from GSD version/GSD revision GSDML V2.3
Configuration control
via dataset No
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Short-circuit protection Yes
Mains buffering
● Mains/voltage failure stored energy time 5 ms
Input current
Current consumption (rated value) 1 A; at 24 V DC and without load
Current consumption, max. 1.7 A
Inrush current, max. 2.8 A
I²t 0.04 A²·s
Power
Infeed power to the backplane bus 14 W
Power loss
Power loss, typ. 3 W
Address area
Address space per module
● Address space per module, max. 64 byte; For input and output data respectively
Address space per station
● Address space per station, max. 64 byte; For input and output data respectively
Hardware configuration
Integrated power supply Yes; 14 W
System power supply can be plugged in to left of IM No
Number of permissible power segments 1; incl. interface module
Rack
● Modules per rack, max. 12; I/O modules
Submodules
● Number of submodules per station, max. 108; 9 per I/O module
Interfaces
Number of PROFINET interfaces 1; 2 ports (switch)
1. Interface
Interface types
● RJ 45 (Ethernet) Yes
● Number of ports 2
● integrated switch Yes
● BusAdapter (PROFINET) No
Protocols
● PROFINET IO Device Yes
● Open IE communication Yes
● Media redundancy Yes; PROFINET MRP client
PROFINET IO Device
Services
— IRT No
— PROFIenergy No
— Prioritized startup No
— Shared device Yes
— Number of IO Controllers with shared device, max. 2
Interface types
RJ 45 (Ethernet)
● Transmission procedure PROFINET with 100 Mbit/s full duplex (100BASE-TX)
● 100 Mbps Yes
● Autonegotiation Yes
● Autocrossing Yes
Protocols
Supports protocol for PROFINET IO Yes
PROFIsafe Yes; FW V4.3.0 or higher
PROFIBUS No
EtherNet/IP No
Modbus TCP No
Redundancy mode
● PROFINET system redundancy (S2) No
— on S7-1500R/H No
— on S7-400H No
● PROFINET system redundancy (R1) No
● H-Sync forwarding No
Media redundancy
— MRP Yes
— MRPD No
Open IE communication
● TCP/IP Yes
● SNMP Yes
● LLDP Yes
Interrupts/diagnostics/status information
Status indicator Yes
Alarms Yes
Diagnostics function Yes
Diagnostics indication LED
● RUN LED Yes; green LED
● ERROR LED Yes; red LED
● MAINT LED Yes; Yellow LED
● Connection display LINK TX/RX Yes; 2x green-yellow LEDs
Potential separation
between backplane bus and electronics No
between PROFINET and all other circuits Yes; 1500 V AC (type test)
between supply and all other circuits No
Permissible potential difference
between different circuits Safety extra low voltage SELV
Isolation
Isolation tested with 707 V DC (type test)
Standards, approvals, certificates
Siemens Eco Profile (SEP) Siemens EcoTech
Network loading class 2
Ecological footprint
● environmental product declaration Yes
Global warming potential
— global warming potential, (total) [CO2 eq] 64.1 kg
— global warming potential, (during production) [CO2 eq] 11.1 kg
— global warming potential, (during operation) [CO2 eq] 53.6 kg
— global warming potential, (after end of life cycle) [CO2 eq] -0.669 kg
Ambient conditions
Ambient temperature during operation
● horizontal installation, min. -30 °C; From FS03
● horizontal installation, max. 60 °C
● vertical installation, min. -30 °C; From FS03
● vertical installation, max. 40 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max. 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Dimensions
Width 35 mm
Height 147 mm
Depth 129 mm
Weights
Weight, approx. 236 g