SIMATIC DP, Connection ET 200M IM 153-2 High Feature for max. 12 S7-300 modules with redundancy capability, Timestamping suitable for isochronous mode New features: up to 12 modules can be used Slave INITIATIVE for Drive ES and Switch ES Expanded quantity structure for HART auxiliary variables Operation of the 64-channel modules 32 signals/slot +++Observe compatibility notes in manual+++

SIMATIC DP, Connection ET 200M IM 153-2 High Feature for max. 12 S7-300 modules with redundancy capability, Timestamping suitable for isochronous mode New features: up to 12 modules can be used Slave INITIATIVE for Drive ES and Switch ES Expanded quantity structure for HART auxiliary variables Operation of the 64-channel modules 32 signals/slot +++Observe compatibility notes in manual+++

Danh mục: SIEMENS Simatic Control Systems Có sẵn
Để biết thêm thông tin, truy cập trang web chính thức của chúng tôi tại geasb.com

Mô tả

General information
Product type designation IM 153-2 DP HF
Firmware version V6.0.0
Vendor identification (VendorID) 801Eh
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
external protection for power supply lines (recommendation) 2,5 A
Mains buffering
● Mains/voltage failure stored energy time 5 ms
Input current
Current consumption, max. 650 mA; with 24 V DC supply
Inrush current, typ. 3 A
I²t 0.1 A²·s
Output current
for backplane bus (5 V DC), max. 1.5 A
Power loss
Power loss, typ. 5.5 W
Address area
Addressing volume
● Inputs 244 byte
● Outputs 244 byte
Hardware configuration
number of modules per DP device interface, max. 12
Time stamping
Accuracy 1 ms; 1 ms at up to 8 modules; 10 ms at up to 12 modules
Number of message buffers 15
Messages per message buffer 20
Number of stampable digital inputs, max. 128; Max. 128 signals/station; max. 32 signals/slot
Time format RFC 1119
Time resolution 0.466 ns
Time interval for transmitting the message buffer if a message is present 1 000 ms
Time stamp on signal change rising / falling edge as signal entering or exiting
Interfaces
Transmission procedure RS 485
Transmission rate, max. 12 Mbit/s
1. Interface
automatic detection of transmission rate Yes
Interface types
● Output current of the interface, max. 70 mA
● Design of the connection 9-pin sub D socket
1st interface / PROFIBUS DP device / header
● GSD file SI05801E.GSG
● automatic baud rate search Yes
Protocols
Bus protocol/transmission protocol PROFIBUS DP to EN 50170
Protocols (Ethernet)
● TCP/IP No
PROFIBUS DP
● Number of node addresses, max. 1 to 125 permitted
Services
— SYNC capability Yes
— FREEZE capability Yes
— Direct data exchange (slave-to-slave communication) Yes; as publisher with all IO, as subscriber with F-IO only
Potential separation
Potential separation exists Yes
Isolation
Isolation tested with Isolation voltage 500 V
Degree and class of protection
IP degree of protection IP20
Ambient conditions
Ambient temperature during operation
● min. 0 °C
● max. 60 °C
● horizontal installation, min. 0 °C
● horizontal installation, max. 60 °C
● vertical installation, min. 0 °C
● vertical installation, max. 40 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max. 3 000 m
configuration / header
Configuration software
● STEP 7 Yes; STEP 7 / COM PROFIBUS / non-Siemens tools via GSD file
Dimensions
Width 40 mm
Height 125 mm
Depth 117 mm
Weights
Weight, approx. 360 g