6AG1132-6BH01-7BA0 SIPLUS ET 200SP DQ 16x24VDC/0,5A ST

6AG1132-6BH01-7BA0 SIPLUS ET 200SP DQ 16x24VDC/0,5A ST

Danh mục: SIEMENS Simatic Control Systems Có sẵn
Để biết thêm thông tin, truy cập trang web chính thức của chúng tôi tại geasb.com

Mô tả

General information
Product type designation DQ 16x24VDC/0.5A ST
Firmware version  
● FW update possible No
based on 6ES7132-6BH01-0BA0
usable BaseUnits BU type A0
Color code for module-specific color identification plate CC00
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode No
Engineering with
● STEP 7 TIA Portal configurable/integrated from version see entry ID: 109746275
Operating mode
● DQ Yes
● DQ with energy-saving function No
● PWM No
● Oversampling No
● MSO No
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption, max. 30 mA; without load
output voltage / header
Rated value (DC) 24 V
Power loss
Power loss, typ. 1 W
Address area
Address space per module
● Address space per module, max. 2 byte; + 2 bytes for QI information
Hardware configuration
Automatic encoding Yes
● Mechanical coding element Yes
● Type of mechanical coding element Type A
Selection of BaseUnit for connection variants
● 1-wire connection BU type A0
● 2-wire connection BU type A0 with AUX terminals or potential distributor module
● 3-wire connection BU type A0 with AUX terminals or potential distributor module
Digital outputs
Type of digital output Source output (PNP, current-sourcing)
Number of digital outputs 16
Current-sinking No
Current-sourcing Yes
Digital outputs, parameterizable Yes
output type acc. to IEC 61131, type 0.5 Yes
Short-circuit protection Yes; Electronic
● Response threshold, typ. 1 A; 0.7 to 1.3 A
Open-circuit detection Yes
Limitation of inductive shutdown voltage to Typ. L+ (-50 V)
Controlling a digital input Yes
Switching capacity of the outputs
● with resistive load, max. 0.5 A
● with inductive load, max. 0.5 A
● on lamp load, max. 5 W
Load resistance range
● lower limit 48 !&
● upper limit 12 k!&
Output current
● for signal "1" rated value 0.5 A
● for signal "1" permissible range, max. 0.5 A
● for signal "0" residual current, max. 0.1 mA
Output delay with resistive load
● "0" to "1", typ. 50 µs
● "1" to "0", typ. 100 µs
Parallel switching of two outputs
● for uprating No
● for redundant control of a load Yes
Switching frequency
● with resistive load, max. 100 Hz
● with inductive load, max. 0.1 Hz; higher frequencies are possible, see Equipment Manual "Maximum permitted switching frequency of inductive loads"
● on lamp load, max. 10 Hz
Total current of the outputs
● Current per channel, max. 0.5 A
● Current per module, max. 8 A; see Equipment Manual "Derating curve"
Total current of the outputs (per module)
horizontal installation
— up to 40 °C, max. 8 A
— up to 50 °C, max. 6 A
— up to 60 °C, max. 4 A
vertical installation
— up to 30 °C, max. 8 A
— up to 40 °C, max. 6 A
— up to 50 °C, max. 4 A
Cable length
● shielded, max. 1 000 m
● unshielded, max. 600 m
Interrupts/diagnostics/status information
Diagnostics function Yes
Substitute values connectable Yes
Alarms
● Diagnostic alarm Yes
Diagnoses
● Monitoring the supply voltage Yes
● Wire-break Yes; Module-wise
● Short-circuit to M Yes; Module-wise
● Short-circuit to L+ Yes; Module-wise
● Group error Yes
Diagnostics indication LED
● Monitoring of the supply voltage (PWR-LED) Yes; green PWR LED
● Channel status display Yes; green LED
● for channel diagnostics No
● for module diagnostics Yes; green/red DIAG LED
Potential separation
Potential separation channels
● between the channels No
● between the channels and backplane bus Yes
● Between the channels and load voltage L+ No
Isolation
Isolation tested with 707 V DC (type test)
Standards, approvals, certificates
Suitable for safety functions No
Suitable for safety-related tripping of standard modules No
Ecological footprint
● environmental product declaration Yes
Global warming potential
— global warming potential, (total) [CO2 eq] 29.3 kg
— global warming potential, (during production) [CO2 eq] 3.98 kg
— global warming potential, (during operation) [CO2 eq] 25.6 kg
— global warming potential, (after end of life cycle) [CO2 eq] -0.245 kg
Ambient conditions
Ambient temperature during operation
● horizontal installation, min. -40 °C; = Tmin (incl. condensation/frost)
● horizontal installation, max. 70 °C; = Tmax; see Derating BasedOn (e.g. manual), additionally Tmax > 60 °C max. total current 1 A
● vertical installation, min. -40 °C; = Tmin
● vertical installation, max. 50 °C; = Tmax
Altitude during operation relating to sea level
● Installation altitude above sea level, max. 5 000 m
● Ambient air temperature-barometric pressure-altitude Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
● With condensation, tested in accordance with IEC 60068-2-38, max. 100 %; incl. condensation / frost permitted (no commissioning under condensation conditions)
Resistance
Coolants and lubricants
— Resistant to commercially available coolants and lubricants Yes; Incl. diesel and oil droplets in the air
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3 Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3 Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3 Yes; Class 3S4 incl. sand, dust, *
— Against mechanical environmental conditions acc. to EN 60721-3-3 Yes; Class 3M8 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6 Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
— to chemically active substances according to EN 60721-3-6 Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6 Yes; Class 6S3 incl. sand, dust; *
— Against mechanical environmental conditions acc. to EN 60721-3-6 Yes; Class 6M4 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Usage in industrial process technology
— Against chemically active substances acc. to EN 60654-4 Yes; Class 3 (excluding trichlorethylene)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04 Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04 * The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
● Coatings for printed circuit board assemblies acc. to EN 61086 Yes; Class 2 for high reliability
● Protection against fouling acc. to EN 60664-3 Yes; Type 1 protection
● Military testing according to MIL-I-46058C, Amendment 7 Yes; Discoloration of coating possible during service life
● Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830A Yes; Conformal coating, Class A
Dimensions
Width 15 mm
Height 73 mm
Depth 58 mm
Weights
Weight, approx. 30 g