| Item | Data | ||||
| APPROVAL | / | ||||
| Test standard | IEC60947-7-1:2009 / UL1059 | ||||
| Pitch [mm] | 15 | ||||
| Poles | 01P | ||||
| IEC60947-7-1 Test data | / | ||||
| Rated voltage [V] | 800 | ||||
| Rated current [A] | 125 | ||||
| Rated connection capacity(solid/stranded) [mm²] | 0.2-35 | ||||
| Surge voltage category/pollution degree/material group | III/3/I | ||||
| Rated impulse voltage [KV] | 8 | ||||
| Rated torque [N.m] | 2.5 | ||||
| UL1059 Test data | / | ||||
| Use group | B | C | D | ||
| Rated voltage [V] | 600 | / | 600 | ||
| Rated current [A] | 85 | / | 5 | ||
| Rated connection capacity(solid/stranded) [AWG] | 12-Feb | ||||
| Rated torque [Lb. in] | 22.15 | ||||
| General data | / | ||||
| Screw | M6 | ||||
| Inflammability class UL94 | V-0 | ||||
| Ambient temperature [℃] | -40~+105 | ||||
| Relative humidity | 5%-95% | ||||
| Inspection standard | MIL-STD-105E II | ||||
| AQL | 0.65 | ||||
| Warranty | 12 months | ||||
| Material and plating | / | ||||
| Housing | PA66 | ||||
| Screws | Copper alloy,Ni plated | ||||
| Contact | Copper alloy,Ni plated | ||||
| Cage | Copper alloy,Ni plated | ||||
| Wire connecting | |||||
| Recommended stripping length 16-17mm; | |||||
| For solid wire, stripping wire to the appointed length, then tightening with rated torque. | |||||
| For stranded wire: stripping wire to the appointed length, mating with corresponding type of ferrule, then tightening with rated torque. | |||||
| Tightening process should be steady, can’t use explosive force. | |||||