In the vertical high-rise landscape of Kuala Lumpur and Selangor, the escape stairwell is the most critical survival zone. Staircase Pressurization is an active fire life-safety system designed to inject fresh air into escape routes, creating a high-pressure shield that physically prevents toxic smoke from entering the stairwell.
EKG M&E Sdn Bhd specializes in the engineering and installation of these systems, ensuring they remain 100% operational to meet the strict mandates of the Uniform Building By-Laws (UBBL), BOMBA standards, and MS 1472:2017.
The primary goal of this system is to maintain a "pressure sandwich"—keeping the air pressure inside the escape stairwell higher than the pressure on the fire floor to ensure a tenable environment.
Under UBBL Section 202 and MS 1472, high-rise buildings (typically those exceeding 45.75 meters in height or those without adequate natural ventilation) must maintain a specific pressure differential.
Static Protection: With all fire doors closed, the system maintains a pressure differential of 50 Pa (Pascals).
Fire-Rated Air Delivery: The air is delivered via 2-hour fire-rated ducts (FRL 120/120/120). This ensures the system continues to pump fresh air even if a floor adjacent to the ducting is on fire.
Active Protection (1.0 m/s): When an occupant opens a fire door to escape, the system must provide an air velocity of at least 1.0 m/s across the open doorway. This acts as an invisible wall, "washing" any smoke away from the entrance.
The 110 N Safety Limit: For the system to be compliant, the force required to open the fire door must not exceed 110 N (Newtons).
As a BOMBA-Compliant M&E Specialist, EKG ensures your pressurization infrastructure supports building efficiency:
TNB Energy Efficiency (Dual-Purpose Optimization):
By ensuring the duct network is Class C Airtight, we minimize static pressure loss. This allows your VFD to maintain required airflows at lower frequencies (Hz) during mandatory weekly testing, directly resulting in a lower monthly TNB electricity bill.
EECA 2024 & Building Compliance:
Under the Energy Efficiency and Conservation Act (EECA) 2024, efficient mechanical transport is a core requirement. Our precision-sealed fire ducts prevent the waste of conditioned air, helping lower your Building Energy Index (BEI).
The "Golden Hour" for Evacuation:
By keeping the stairwell clear of smoke and heat, our systems provide the "Golden Hour" needed for occupants to exit safely and for BOMBA personnel to navigate the building for rescue and firefighting.
| Feature | Natural Ventilation | EKG Staircase Pressurization |
| Height Requirement | Low-to-Mid Rise | High-Rise (>45.75m per UBBL) |
| Primary Goal | Passive Smoke Release | Active Smoke Rejection |
| Required Pressure | Neutral | 50 Pa (Pascals) Differential |
| Open Door Velocity | N/A | 1.0 m/s (MS 1472 Standard) |
| BOMBA Inspection | Visual Only | Mandatory Flow & Pressure Tests |
Total 3D BIM Coordination: High-rise shafts are extremely congested. We utilize 3D modeling to route fire-rated ducts through crowded spaces, ensuring zero "clashes" with sprinklers, standpipes, or structural beams.
Turnkey BOMBA Submission: We perform the mandatory Pressure Differential Test, Door Opening Force Test, and Anemometer Airflow Traverse required for your Fire Certificate (FC) application and annual renewals.
Strategic Regional Support: Based in Kuala Lumpur, we provide professional pressurization services for Grade-A office towers, luxury condominiums, and hospitals across the region.
Is your high-rise escape route protected by a compliant, high-performance pressurization system? Contact EKG M&E Sdn Bhd today for a professional fire-rated ducting audit and technical proposal.