| Measuring Principle | Energy manager | |
| Function | Monitoring and billing of energy in heating and cooling applications as well as combined heating-and cooling circles. Typical applications can be found in industries, district heating and building automation. |
|
| Certification | CE, UL listed, CSA GP, MID 004 (custody transfer) according EN1434 (water/other liquids) and OIML R75 | |
| Input | 1x Puls/Analog, 2x RTD/Analog, Loop power supply 24V DC (+/-16%) |
|
| Output | 1x 4...20mA, 2x digital (Open Collector) |
|
| Relay output | 2x | |
| Auxiliary power supply | Low voltage power supply: 100 bis 230 V AC (-15% / +10%); Small voltage power supply: 24 V DC (-50% / +75%), 24 V AC (±50%) | |
| Dimensions (wxhxd) | 144 x 144 x 103.1 mm (5.67'' x 5.67'' x 4.06'') |
|
| Software | Calculated Values: Energy, volume, density, enthalpy & enthalpy difference, DP-Flow-Compensation, mass, temperature difference; Counters: volume, mass, energy, counter in case of failure Optional: tariff 1, tariff 2 or seperated heating energy, cooling energy, bilance energy |
|
| Operation | 3 button on site or via FieldCare; read out of historical / logged data via Field Data Manager Software (SQL database and visualization interface), selectable language | |
| Display | 160 x 80 Dot-Matrix LCD with white backlit, colour change in case of alarm event, active display area 70 x 34 mm | |
| Others | electronic temperature sensor matching via CvD coefficients, logbook measured values, custody transfer logbook, event logbook, limit monitoring | |
| Calculations | IAPWS-IF97 | |
Malaysia