Circutor CVM-C4 Power Analyzer
Product model: CVM-C4-ITF-485-ICT2 | Code: M52706
| Application Area | How CVM-C4 Helps |
| Compact electrical panels | Suitable for panels with limited installation depth or limited front panel space. |
| Electrical parameter monitoring | Displays instantaneous values of key electrical parameters locally on the LCD screen. |
| SCADA / EMS integration | RS-485 Modbus RTU enables remote data collection and centralised monitoring. |
| Energy metering | Logs consumed or generated active and reactive energy. |
| Alarm and local control | Relay outputs can be programmed to activate based on alarm conditions. |
| Tariff or source separation | Digital inputs can be used to measure energy from two different sources or tariffs. |
| Harmonic visibility | Voltage and current THD% measurements help check harmonic presence in the installation. |
| Feature | Datasheet Detail | Webpage Value |
| Panel mounting | 96 x 96 mm, 41.5 mm depth | Compact installation for low-voltage panels and retrofit applications. |
| Network support | Single-phase and three-phase networks, with or without neutral | Flexible use across common electrical distribution configurations. |
| Measurement method | True RMS measurement | More reliable reading under non-ideal electrical conditions. |
| Current input | .../5 A | .../1 A | Works with standard external CT ratios. |
| Voltage input | 3 AC voltage inputs | Measures the main voltage parameters for three-phase systems. |
| Communication | RS-485, Modbus RTU | Suitable for SCADA, EMS, BMS and remote monitoring systems. |
| Relay outputs | 2 relay outputs | Supports local alarm or control actions. |
| Digital inputs | 2 potential-free digital inputs | Useful for source/tariff selection and dual energy metering. |
| Transistor outputs | 2 passive impulse outputs | Supports energy pulse output applications. |
| Harmonic check | Voltage and current THD% | Basic harmonic visibility for installation health checks. |
| Parameter | Value |
| Product family | CVM-C4 |
| Model | CVM-C4-ITF-485-ICT2 |
| Code | M52706 |
| Product type | Power analyzer / multifunctional multimeter for panel |
| Mounting | Panel |
| Protocol | Modbus RTU |
| Communication | RS-485 |
| Measuring current channels | 3 |
| Input current | .../5 A | .../1 A |
| Transistor outputs | 2 |
| Relay outputs | 2 |
| Digital inputs | 2 |
| Parameter | Value |
| AC nominal voltage | 80 ... 270 Vac |
| AC frequency | 50/60 Hz |
| AC consumption | 6 ... 18 VA |
| AC installation category | CAT III 300 V |
| DC nominal voltage | 80 ... 270 Vdc |
| DC consumption | 1.5 ... 1.8 W |
| DC installation category | CAT III 300 V |
| Parameter | Value |
| Dimensions | 96 x 96 x 41.5 mm |
| Envelope | Polycarbonate + ABS |
| Torque setting | 0.5 Nm |
| Terminal cable gauge | 2.5 mm2 |
| Weight | 0.268 kg |
| Protection class | Front: IP54, Rear: IP20 |
| Relative humidity | 5 ... 95%, without condensation |
| Storage temperature | -20 ... +70 °C |
| Operating temperature | -10 ... +60 °C |
| Parameter | Value |
| Installation category | CAT III 300 V |
| Nominal current | 1 A / 5 A AC |
| Consumption | < 0.2 VA per phase |
| Allowable overload | 1.2 In continuous, 10 In instantaneous for 5 s |
| Parameter | Value |
| Installation category | CAT III 300 V |
| Nominal voltage | 100 ... 277 V Ph-N, ±8% |
| Sampling / frequency range | 45 ... 65 Hz |
| Input impedance | > 1.7 MΩ |
| Consumption | < 0.2 VA per phase |
| Maximum permanent measurement voltage | 1.2 Un continuous, 2 Un instantaneous |
| Parameter | Value |
| Protocol | Modbus RTU |
| Interface | RS-485 |
| Speed | 2400 / 4800 / 9600 / 19200 bps |
| Data bits | 8 |
| Stop bits | 1-2 |
| Parity | None / Even / Odd |
| Parameter | Value |
| Display type | LCD |
| Keyboard | 3 keys |
| Digital inputs | 2 potential-free contacts |
| Digital input insulation | 3.75 kV RMS |
| Maximum short-circuit current | 4 mA |
| Maximum open circuit voltage | 30 V |
| Relay outputs | 2 relay outputs |
| Relay resistive load | 250 Vac / 5 Aac, 30 Vdc / 5 Adc |
| Relay maximum switching capacity | 1385 VA / 150 W |
| Transistor output type | Passive impulse |
| Transistor maximum frequency | 10 Hz |
| Transistor maximum current | 27 mA |
| Transistor maximum voltage | 27 Vdc |
| Parameter | Value |
| Frequency | 0.5% |
| Phase current | 0.2% |
| Phase voltage | 0.2% |
| Active power | 0.5% |
| Reactive power | 0.5% |
| Active energy | 0.5% |
| Reactive energy | 0.5% |
| Parameter | Value |
| Electrical safety maximum height | 2000 m |
| Electrical safety installation category | CAT III 300 V |
| Contamination level / class | Pollution resistance 2 |
| Standards | IEC 61010-1, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11 |
| Code | Type | Input Current | Transistor Output | No. Relays | Digital Inputs | Communication | Protocol |
| M52706 | CVM-C4-ITF-485-ICT2 | .../5 A | .../1 A | 2 | 2 | 2 | RS-485 | Modbus RTU |