HI510-0320 Universal Controller with Digital Probe Inputs, 3 relays, 2 analog outputs

HI510-0320 Universal Controller with Digital Probe Inputs, 3 relays, 2 analog outputs

分类: Controllers & Transmitters 当前有货 (数量:1)
Option
HI510-0320 Universal Controller with Digital Probe Inputs, 3 relays, 2 analog outputs
可在官方网站购买
欲了解更多详情,请游览我们的官方网站 hannamalaysia.com

详情

HI510
Universal Process Controller


HI510 is an advanced universal process controller that can be configured for many applications requiring monitoring and/or control of process parameters. This controller features a digital probe input that will automatically detect and update the meter with the parameter that it measures.

 

 
HI510_angleright

Control Modes

Set points for control operations can be configured to be on/off, proportional, or PID types of control. The flexibility in programming allows for fine-tuning of a set point to be maintained with tight control preventing any overshoot and waste of chemicals.

Hold Function

Hold can also be triggered manually and by using and external digital input for disabling control mode when performing maintenance.

Configurable Alarm System

Configurable for set points and temperature or activated by abnormal operation, a red Alarm LED will blink and can easily be seen from a distance. All relays configured for control are inactivated until the alarm state is resolved.

Auto-cleaning cycle

The cleaning function allows the ability to program one or more wash cycles and use the relays to activate valves, pumps or compressed air based on the type of washing that is required to maintain probes for reliable results.
 


HI510_controller_relays

Relays

Available with up to five control and one alarm electromechanical relays.

Analog Outputs

Up to four galvanically isolated analog outputs for control of pumps and valves.

Digital RS485 Output

Can daisy-chain up to 32 devices to a remote monitoring system.

Digital Inputs

Two digital inputs available for modes including disabling, cleaning and placing the controller into hold status.
 


HI510_controller_hold

Large LCD

The LCD displays measurement information along with indicators of potential problems. The DIAG key then provides details of the issue.

HI510_controller_logging

Data-logging

Store info at selectable intervals along with relay control settings and calibrations data.  up to 100 lots, each holding 8600 records. Transfer to a flash drive as a .csv file using the USB Type-C port.

HI510_controller_diagnostic

Help Button

Using the help and diagnostic button (? DIAG) will provide information related to errors or in setup mode, information about settings.
 


SPECIFICATION

Specification Detail
sku HI510
Display Graphic LCD,
128 x 64 pixel B/W with backlight
digital inputs 2 independent,
galvanically isolated inputs,
configurable for Hold & Cleaning functions
On state: 5 to 24 Vdc,
low or high level active
Analog outputs 2 or 4 independent outputs
0 - 22 mA configurable as:
  • 0 - 20mA
  • 4 - 20mA
  • 22 mA as alarm signal
Analog output Accuracy ±0.2% f.s.
Digital Communication
  • RS-485 serial port for remote monitoring and control
  • USB-C port to retrieve log files and firmware upgrades
Relays Up to 5 relays,
independently configurable for process variables,
Hold and CLeaning Functions
Electromechanical relay SPDT and SPST contact outputs
5A - 250 VAC,
5A - 30 Vdc (resistive load)
Fuse protected: 5A,
250V slow blow
Alarm relay for all measurement alarms Electromechanical relay SPDT contact output
5A - 250 Vac,
5A - 30 Vdc (resistive load)
Fuse protected: 5A,
250V slow blow fuse
Data logging
  • Interval log,
    up to 100 files,
    maximum 8600 records on each stored file. When the maximum limit is reached,
    the most recent file with automatically erase the oldest one.
  • Event log,
    maximum 100 records. When the maximum limi
Power Supply 100 - 240 Vac ± 10%,
50/60 Hz,
15VA
Power consumption 15VA
Installation category II
Enclosure* Single case 1/2 DIN,
type 4x IP65 ingress protection
Weight Approximately 1.6 kg,
(3.5 lb.)
Dimensions Width: 144.0 mm (5.7 in.)
Height: 144.0 mm (5.7 in.)
Depth: 151.3 mm (6.0 in.)
Environment -20 to 50°C (-4 to 122°F),
maximum 100% RH non-condensing
Note *For a water tight seal,
tighten the four front casing screws to 13.3 lbf-in (1.5 N-m,
maximum 2.0 N-m) of torque

更多 Hanna Instruments (M) Sdn Bhd 相关资料
Hanna Instruments (M) Sdn Bhd
Hanna Instruments (M) Sdn Bhd Measuring Instruments Selangor, Photometers Supply Penang, Sabah, Test Equipments Supplier Malaysia ~ Hanna Instruments (M) Sdn Bhd