Description
        HONEYWELL V4043; V4044 FAN COIL VALVES 2-WAY AND 3-WAY
Spring Return Type
Spring return VC valve is one type of control valve that can do precise control refer to customer’s demands. Spring return actuator has the special function that if the power is off, the valve will return to original position by spring. This is a safe and energy saving function to customers.  
Model
HONEYWELL V4043C1347B 2-WAY (BSPP INT. 1/2'') FAN COIL VALVE
HONEYWELL V4043C1362B 2-WAY (BSPP INT. 3/4'') FAN COIL VALVE
	HONEYWELL V4043C1339 2-WAY (BSPP INT. 1'') (2-WIRE 220V 50HZ 6W) FAN COIL VALVE
	 
	HONEYWELL V4044A1704B 3-WAY (3/4'' BSPT [INT. THREAD]) (2-WIRE 220V 50HZ 6W) FAN COIL VALVE * 8-WEEK LEAD TIME!
HONEYWELL V4044C1668B 3-WAY (1/2'' BSPT [INT. THREAD]) (2-WIRE 220V 50HZ 6W) FAN COIL VALVE * 8-WEEK LEAD TIME!
The V4044 Motorised Diverter Valve has been designed to control the flow of water between heating and hot water in domestic fully pumped central systems. The Diverter Valve will only allow flow to one zone at any one time. The V4044 is used in the Sundial W Plan Hot Water priority system.
	Features
	- 
		Spring return action
- 
		Two position operation
- 
		Powerhead replaceable without draining down
- 
		Manual lever for filling/draining down
- 
		Quiet operation, minimal power consumption
	 
	Options
	- 
		22mm/28mm or 1/2'', 1'' connections
- 
		Replacement motor/powerhead/ball and 'O' ring kit
Packing
10-pc/box
	FEATURES
	 
	• The V4043 provide 2-position, 2-way straight through control of water
	• The V4044 provide 2-position 3-way diverting control of water.
	• Compact construction for easy installation.
	• Manual opener for valve operation on power failure. Valve returns to automatic position when power is restored. (Note : Spring Return)
	• Choice of BSPP or flare fitting brass end connections for standard copper tubing.
	• Motor can be replaced by removing one screw, without disturbing the valve body or draining the system.
	• Complete powerhead may be removed or replaced without breaking the line connections or draining the system.
	• All models can be installed without disassembling the valve.
	• Fits under the cover of most baseboards. 
	
	Note:
	V4043 comply with PN16
	
	
		SPECIFICATIONS
		 
	
		Power Supply: 220 Vac, 50 Hz
	
		Power Consumption: 6W
	
		Timing (nominal):
	
		On: 12 seconds under power
	
		Off: 6 seconds under spring return
	
		Flow Characteristics:
	
		Quick opening for on-off application
	
		Ambient Temperature: 1-50 °C
	
		Fluid Temperature: 5-94 °C
	
		Serviced Medium:
	
		Suitable for hot and chilled water with up to 50%
	
		glycol
	
		Material:
	
		Valve Body: Forged Brass 
		
		
			APPLICATION
			 
		
			These valves consist of an actuator motor and
		
			valve assembly for controlling the flow of hot or
		
			chilled water in commercial HVAC equipment
		
			such as fan coil units, terminal reheat coils and
		
			convectors.
			 
		
			IMPORTANT
			 
		
			These valves are not for use in systems
		
			containing dissolved oxygen. 
			
			
		 
	 
 
        More detail about Culmi Air-Cond & Refrigeration Parts Supply Sdn Bhd