| Item | Data | |||
| APPROVAL | ||||
| Test standard | IEC/EN60998-1:2004 / UL1059 | |||
| Pitch [mm] | / | |||
| Poles | 01P | |||
| EN60998 Test data | VDE certificate NO. 40024836 | |||
| Rated voltage [V] | 750 | |||
| Rated current [A] | 32 | |||
| Rated connection capacity(solid/stranded) [mm2] | 0.5~4 | |||
| Surge voltage category/pollution degree/material group | III/2/I | |||
| Withstanding Voltage [KV/min] | 2 | |||
| Rated torque [N·m] | 0.8 | |||
| UL1059Test data | UL File Number E228872 | |||
| Use group | B | C | D | |
| Rated voltage [V] | 300 | 300 | / | |
| Rated current [A] | 20 | 20 | / | |
| Rated connection capacity) (solid/stranded [AWG] | 20~10 | |||
| Rated torque [Lb. in] | 7.02 | |||
| General data | / | |||
| Screw | M3.5 | |||
| Inflammability classUL94 | V-0 | |||
| Ambient temperature [℃] | -40~+105 | |||
| Relative humidity | 5%-95% | |||
| Inspection standard | MIL-STD-105E II | |||
| AQL | 0.65 | |||
| Warranty | 12 months | |||
| Material and plating | / | |||
| Housing | PA66 | |||
| Screws | Steel,Zn plated | |||
| Contact | Copper alloy,Sn plated | |||
| Cage | Copper alloy,Ni plated | |||
| Wire connecting | ||||
| 10-12mm; Recommended stripping length 10-12mm; | ||||
| 1.For solid wire, stripping wire to the appointed length, then tightening with rated torque. | ||||
| 2.For stranded wire: stripping wire to the appointed length, mating with corresponding type of ferrule, then tightening with rated torque. | ||||
| Tightening process should be steady, can’t use explosive force. | ||||