Description
        CN20, CN34 SERIES NON-SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS FOR MODULATING AND FLOATING / 2-POSITION CONTROL 
Model (Acuator)
	HONEYWELL CN4620A1001 20NM, 230VAC, DAMPER ACTUATOR, NON-SPRING RETURN
CN7220A2007 20Nm,24Vac/Vdc, Modulating and floating/2-position control, Non-Spring return, Voltage Feedback Signal and without aux. Switch
CN7234A2008 34Nm,24Vac/Vdc, Modulating and floating/2-position control, Non-Spring return, Voltage Feedback Signal and without aux. Switch
	HONEYWELL CN7234A2008 34NM, 24VAC/VDC, MODULATING CONTROL, NON-SPRING RETURN (FAIL SAFE FUNCTION) Voltage Feedback Signal AND without aux. Switch
	 
Model (Ball Valve)
	
		HONEYWELL VBA216-100F 2-WAY DN100 (4'') PN16 KVS160 FLANGED BALL VALVES (TEMP:-5~120°C)
	
		 
	Complete Set
	
	
		HONEYWELL CN7234A2008 34NM, 24VAC/VDC, MODULATING CONTROL+VBA216-100F 2-WAY DN100 (4'') PN16 KVS160 FLANGED BALL VALVES (TEMP:-5~120°C)
	
		 
 
Controller To Use
Can use TB7980A, TF243WN or TFM223N/U, depending if you want any external duct sensor or 3-speed fan switch.
	GENERAL
	 
	These direct-coupled damper actuators provide modulating control for:
	• air dampers,
	• VAV units,
	• air handling units,
	• ventilation flaps,
	• louvers, and
	• reliable control for air damper applications with up to 4.6 m2
	 / 50 sq.ft. (20 Nm / 177 lb-in) or 7.8 m2
	 / 85 sq. ft.
	(34 Nm / 300 lb-in) (seal-less dampers; air frictiondependent).
	 
	FEATURES
	 
	• Self-centering shaft adapter
	• Access cover to facilitate connectivity
	• Service/off for safe & easy servicing
	• Rotation direction selectable by switch
	• Declutch for manual adjustment
	• Mechanical end limits
	• Field-installable auxiliary switches
	• Mountable in any orientation (no IP54 if upside down)
	• Mechanical position indicator
	• CE and UL certified
	
	
		SPECIFICATIONS
		 
	
		Supply voltage 24 Vac/dc ±15%, 50/60 Hz;
	
		 
	
		Nominal voltage 24 Vac/dc, 50/60 Hz;
	
		All values stated hereinafter apply to operation under
	
		nominal voltage conditions.
	
		Power consumption
	
		CN7220A2007 6 VA / 3 W
	
		CN7234A2008 6 VA / 3 W
	
		Ambient limits
	
		Ambient operating limits -20...+60 °C (-5...+140 °F)
	
		Ambient storage limits -40...+80 °C (-40...+175 °F)
	
		Relative humidity 5...95%, non-condensing
	
		Safety
	
		Protection standard IP54 as per EN 60529
	
		Protection class II as per EN 60730-1
	
		Overvoltage category II
	
		Lifetime
	
		Full strokes 60000
	
		Repositions 1.5 million
	
		Mounting
	
		Round damper shaft 10...27 mm (3/8...1-1/16')
	
		Square damper shaft 10...18 mm (3/8...11/16');
	
		 45° steps
	
		Shaft length min. 22 mm (7/8')
	
		Control signal 0(2)...10 Vdc
	
		 0(4)...20 mA
	
		Input impedance >100 kΩ [0...10 V]
	
		 500 Ω [0...20 mA]
	
		Feedback signal
	
		Limits ± 1 mA at 0...10 V
	
		End switches (when included)
	
		Rating 5 A (resistive) / 3 A (inductive)
	
		Triggering points 5° / 85°
	
		Torque rating
	
		CN7220A2007 20 Nm (177 lb-in) 
		
			CN7234A2008 34 Nm (300 lb-in)
		
			Runtime 95 sec (60 Hz) / 110 sec (50 Hz
		
			or DC supply)
		
			Rotation stroke 95° ± 3°
		
			Dimensions see 'Dimensions' on page 8
		
			Weight (without cables) 1.35 kg (3 lbs.)
		
			Noise rating 40 dB(A) max. at 1 m
		
			Certification CE & UL
			
			Torque Per Module (Nm) Calculation
			
			NON-SPRING RETURN (ON/OFF)
			e.g : a) 200 x 200 (mm) [Damper Size (Net)] = 0.2 x 0.2 = 0.04 M2
			        x 10 (Factor) = 0.4 Nm
			
			MFD-S (Motorized Fire Damper) Fail Safe Fast Running (SPRING RETURN)
			e.g : a) 1,200 x 600 (mm) = 1.2 x 0.6 = 0.72 M2
			         x 10 (Factor) = 7.2 Nm
			
			         b) 1,500 x 1,200 (mm) = 1.5 x 1.2 = 1.8 M2
			         x 10 (Factor) = 18 Nm
			
			         c) 2,500 x 1,000 (mm) = 2.5 x 1.0 = 2.5 M2
			         x 10 (Factor) = 25 Nm
			 
	 
 