HONEYWELL ML7421A8035-E 24V 50/60HZ DIRECT COUPLED ELECTRIC VALVE ACTUATOR 
	
	Note
	
	ML7421A8035 can be used up to a max 3'' valve only
	
	
		What is a Modulating Control Valve?
	
	
		A modulating control valve is an automated valve that is used to control the amount of flow in a system or process. They go beyond simple shutoff or isolation (on/off) and actually allow precise control of the flow rate. The actuators on these valves use feedback and control signals to accurately open and close the valve. 
	
	Note
	1) ML7421A is for big valve.Torque is 1,800Nm. ML7420A8088A is for 1.5'' and below. Torque is 600Nm.
	2) Pls note that there is no performance warranty on ML7420A with V5011P1038 (2'' 2-Way). It may not be strong enough to close the valve after a while. 
	3) All modulating actuators/thermostats are automatically 24Vac. This is industry standard.
	
	Note
	Replaced ML7421A1032 model
	Replaced ML7421A3004 model
	Replaced ML7421A1008 model
	
	Complete Set
	
	
		
			HONEYWELL V5013P1028 DN50 2'' 3-WAY BRONZE AHU VALVE C/W ML7421A8035-E MODULATING ACTUATOR
			
				HONEYWELL V5329A2077 DN65 2-1/2'' 3-WAY VALVE + ML7421A8035-E 24V ELECTRICAL VALVE ACTUATOR
		 
		HONEYWELL V5329A 2-1/2'' 3-WAY CI AHU VALVE C/W ML7421A (1,800N) MODULATING ACTUATOR * Note: ML7984A (710N) is not recommended for 2.1/2'' 3 way valve. Torque not strong enough.
		
			 V5329A/ML7421A- 3'' 3 Way valve c/w mod actuator
		
			 V5328A/ML7421A - 3'' 2 way valve c/w mod actuator
			
			New Combination With New Valve Types
			
			The valve for 3'' 3-Way is V5GV3W080F and the valve for 2-Way is V5GV2W080F. You can still use back the same ML7421A Actuator
		
			 
	 
	
	
		
			GENERAL
			 
		
			
				The ML7421A / ML7421B actuators are designed for modulating control, accepting 0(2)...10v or 4...20mA input
			
				signal, and providing feedback signal 2...10 Vdc only. They operate Honeywell’s standard valves in heating, ventilation,
			
				and air conditioning (HVAC) applications.
		 
		
		FEATURE
		  
	
		 Easy and quick installation
	
		 No separate linkage and adjustments required
	
		 Low power consumption and maintenance-free
	
		 Self-adaption function
	
		 Force-limiting end stops
	
		 Manual operation knob
	
		 0(2)~10 Vdc input and 2~10 Vdc position feedback
	
		 Direct/ Reverse action adjustable
	
		 Selectable stroke position when signal failure
	
		 Corrosion-resistant design
		
		
			SPECIFICATION
			 
		
			Temperature
			 
		
			Ambient operating -10~+50℃ at 5~95% r.h.
		
			Ambient storage -40...+70 °C at 5...95% r.h.
		
			Medium temperature 150 °C max. (220 °C with
		
			High-Temperature kit)
			 
		
			Signals
			 
		
			Signal input y=0(2)~10 Vdc or 4~20 mA
		
			Input impedance for voltage Ri=100 KΩ
		
			for mA Ri=500Ω
		
			Position feedback signal x=2~10Vdc
		
			Output impedance 1 KΩ max.
		
			Output load 1 mA max.
			 
		
			Safety
			 
		
			Protection class III as per EN60730-1
		
			Protection standard IP54 as per EN60529
		
			Flame retardant housing V0 as per UL94
		
			(with metal cable gland)
			 
		
			Material
			 
		
			Cover ABS-FR
		
			Yoke and Base Aluminum die-cast