Differential Pressure Sensor Calibration

Differential Pressure Sensor Calibration

分类: Pressurization Fan Maintenance 当前有货
欲了解更多详情,请游览我们的官方网站 eakon.com.my

详情

Differential Pressure Sensor Calibration | Pressurization Fan Maintenance by EKG

In a high-rise staircase pressurization or smoke spill system, the Differential Pressure (DP) Sensor is the "brain" of the operation. It tells the Variable Frequency Drive (VFD) how fast to spin to maintain the life-saving 50 Pa (Pascals) of pressure required by BOMBA. In Kuala Lumpur’s humid climate, these sensors often suffer from "drift" or tube blockages, leading to fans that either under-pressurize (allowing smoke in) or over-pressurize (making exit doors impossible to open).

As part of a Ventilation Systems Audit, EKG performs precision calibration to ensure your safety fans respond with surgical accuracy during a fire.


1. The Critical Role of the DP Sensor

The DP sensor measures the difference between the "Safe Zone" (stairwell) and the "Fire Zone" (lobby/corridor).


2. The EKG "Precision-Zero" Calibration Protocol

We use laboratory-grade pressure calibrators to re-align your sensors to 2026 safety standards:


3. The Energy & Mechanical Impact: The Cube Law

A miscalibrated sensor wastes massive amounts of energy during testing and "Purge" cycles.


4. Sensor Health & Compliance Matrix

Condition Observation Resulting Risk
Calibrated Matches Master Gauge (+/- 2 Pa) BOMBA Compliant / Safe Exit
Positive Drift Reads 10 Pa when fan is OFF Under-Pressurization (Smoke Leak)
Negative Drift Reads -5 Pa when fan is OFF Over-Pressurization (Stuck Doors)
Blocked Tube Zero movement when fan starts System Fault / VFD Trip
Moisture in Line "Jumping" or unstable readings Fan Hunting / Motor Wear

5. Why Trust EKG for Sensor Calibration?