In the high-density developments of KL and PJ, fire safety ventilation is the most critical life-safety component of a building's M&E infrastructure. Standard air conditioning is designed for comfort, but Fire Safety Ventilation is engineered to manage toxic smoke and extreme heat. EKG M&E Sdn Bhd specializes in integrated smoke control systems that meet the strict BOMBA and Uniform Building By-Laws (UBBL) requirements.
Effective fire ventilation requires a "Total System" approach where fans, dampers, and sensors work in perfect synchronization to protect occupants.
In a fire, smoke inhalation is the primary danger. We install high-capacity axial fans designed to "flush" the fire zone.
10 Air Changes Per Hour (ACH): We engineer the system to meet the mandatory 10 ACH rate, rapidly removing toxic gases to maintain a "Clear Layer" for evacuation.
High-Temperature Reliability: Our fans utilize Class H motors, certified to operate at 250 degrees Celsius for 2 hours.
To keep escape routes 100% smoke-free, we utilize Positive Pressure.
The Pressure Shield: We pump fresh outdoor air into stairwells to maintain a pressure of 50 Pa. This ensures that when a fire door opens, air blows out, preventing smoke from entering the exit path.
VFD Response: We integrate Variable Frequency Drives (VFDs) that automatically ramp up fan speed when doors are opened, maintaining the air curtain effect without over-pressurizing the shaft when doors are closed.
To prevent the HVAC ductwork from acting as a "highway" for fire, we install specialized barriers:
Motorized Fire Dampers: Installed at fire-rated wall penetrations, these dampers are interlocked with the Main Fire Alarm Panel (MFAP) to snap shut instantly.
Fire-Rated Ducting: We utilize heavy-gauge or coated ducting (BS 476-24) to ensure the extraction path remains structurally sound under intense heat.
| System Feature | UBBL / BOMBA Requirement | EKG M&E Standard |
| Extraction Rate | 10 ACH (Smoke Spill). | High-Static Axial Performance. |
| Response Time | Activation within 60 seconds. | High-speed motorized actuators. |
| Pressurization | 50 Pa (Stairwells). | Calibrated Pressure Mapping. |
| Power Supply | Secondary/Genset backed. | Fire-rated cables and ATS. |
HVAC & Clean Air Specialist: We ensure your "Smoke Mode" logic is flawless. When the smoke fans activate, the general office AC must shut down to prevent the mechanical mixing of smoke into unaffected rooms.
Testing and Commissioning (T&C): We don't just "install and leave." We provide professional Smoke Visualization Testing and Differential Pressure Audits to prove your building is 100% safe before your annual Fire Certificate (FC) renewal.
Klang Valley Strategic Support: Based in Kuala Lumpur, we provide priority 24/7 maintenance and emergency response for smoke control systems across the Klang Valley.