Contactor MC18B

Contactor MC18B

分类: ELECTRICAL 当前有货
欲了解更多详情,请游览我们的官方网站 cs.net.my

详情

MC18B Contactor


MC18B vs MC32A

Feature MC18B MC32A
Motor size Up to ~2.0 HP Up to ~3–5 HP
Use Smaller motors Larger motors
Pairing Works with MT-32 relays Works with MT-32 relays

For a 2.0 HP motor, MC18B is a very good match — often better sized than MC32A, which is sometimes oversized for this power.


MC18B Work With MT-32 Overload

Yes — MC18B can be paired with the MT-32 thermal overload relay (like your MT323H), just like MC32A.

You set the overload relay based on the motor’s Full Load Amp (FLA):

  1. Contactor (MC18B): switches motor ON/OFF

  2. Overload (MT323H): protects against overcurrent

Together they form your D.O.L Starter

1. Motor Full Load Amps

Check the motor nameplate. Example typical FLA:

Motor Voltage FLA (approx)
2.0 HP 240 V (1φ) ~10–12 A
2.0 HP 415 V (3φ) ~3.0–4.0 A

3. Set Overload Relay

Turn the MT-323H dial to match the motor’s FLA exactly.


Recommended Starter Setup for 2.0 HP

Component Recommended
Contactor MC18B
Overload relay MT323H (set to motor FLA)
Starter type D.O.L Starter
Coil voltage Match your control supply (240 V / 110 V etc.)