| Detailed Specifications | 
																			
																				| General | 
																			
																				| Display:1999 digit LCD | Display with special symbols, digit height 25 mm, fluorescent backlight | 
																			
																				| User interface | Instant measurement through TURN and START one button concept. The only operating elements are rotary switch and START button | 
																			
																				| Robust, water and dust resistant | Instrument is designed for tough environmental conditions (rubber protective cover, IP56) | 
																			
																				| Memory | Internal memory storage up to 1500 records accessible via USB port | 
																			
																				| Temperature Range | 
																			
																				| Operating temperature | -10 °C to 50 °C (14 °F to 122 °F) | 
																			
																				| Storage temperature | -30 °C to 60 °C (-22 °F to 140 °F) | 
																			
																				| Temperature coefficient | ± 0.1 % of reading/°C <18 °C >28 °C | 
																			
																				| Intrinsic error | Refers to the reference temperature range and is guaranteed for 1 year | 
																			
																				| Operating error | Refers to the operating temperature range and is guaranteed for 1 year | 
																			
																				| Climatic class | C1 (IEC 654-1), -5 °C to +45 °C (23° to +115° F), 5 % to 95 % RH | 
																			
																				| Protective type | IP56 for case, IP40 for battery door according to EN60529 | 
																			
																				| Safety | Protection by double and/or reinforced insulation. max. 50 V to earth. IEC61010-1: Pollution degree 2 | 
																			
																				| EMC (emission immunity) | IEC61326-1: Portable | 
																			
																				| Quality system | Developed, designed and manufactured according to DIN ISO 9001 | 
																			
																				| External voltage | V ext, max = 24 V (dc, ac < 400 Hz), measurement inhibited for higher values | 
																			
																				| V ext rejection | > 120 dB (162⁄3, 50, 60, 400 Hz) | 
																			
																				| Measuring time | Typical 6 seconds | 
																			
																				| Max. overload | 250 V rms (pertains to misuse) | 
																			
																				| Auxiliary power | 6 x 1.5 V Alkaline (type AA LR6) | 
																			
																				| Battery life span | Typical > 3,000 measurements | 
																			
																				| Dimensions (WxHxD) | 250 mm x 133 mm x 187 mm (9.75 in x 5.25 in x 7.35 in) | 
																			
																				| Weight | 1.1 kg (2.43 lb) including batteries 7.6 kg (16.8 lb) incl. accessories and batteries in carrying case
 | 
																			
																				| RA 3-Pole Ground Resistance Measurement (IEC 1557-5) | 
																			
																				| Switch position | RA 3-pole | 
																			
																				| Resolution | 0.001 Ω to 10 Ω | 
																			
																				| Measuring range | 0.020 Ω to 19.99 kΩ | 
																			
																				| Accuracy | ± (2 % rdg + 3 d) | 
																			
																				| Operating error | ± (5 % rdg + 3 d) | 
																			
																			
																			
																				| Measuring Principle: Current and Voltage Measurement | 
																			
																				| Measuring voltage | Vm = 48 V ac | 
																			
																				| Short-circuit current | > 50 mA | 
																			
																				| Measure frequency | 128 Hz | 
																			
																				| Probe resistance (RS) | Max 100 kΩ | 
																			
																				| Auxiliary earth electrode resistance (RH) | Max 100 kΩ | 
																			
																				| Additional error from RH and RS | RH[kΩ]•••RS[kΩ]/RA[Ω]•••0.2 % | 
																			
																				| Monitoring of RS and RH with error indicator. Automatic range selection.
 Measurement is not performed if the current through the current clamp is too low.
 | 
																			
																				| RA 4-Pole Ground Resistance Measurement (IEC 1557-5) | 
																			
																				| Switch position | RA 4-pole | 
																			
																				| Resolution | 0.001 Ω to 10 Ω | 
																			
																				| Measuring range | 0.020 Ω to 19.99 kΩ | 
																			
																				| Accuracy | ± (2 % rdg + 3 d) | 
																			
																				| Operating error | ± (5 % rdg + 3 d) | 
																			
																				| Measuring Principle: Current and voltage Measurement | 
																			
																				| Measuring voltage | Vm = 48 V ac | 
																			
																				| Short-circuit current | > 50 mA | 
																			
																				| Measure frequency | 128 Hz | 
																			
																				| Probe resistance (RS +RES) | Max 100 kΩ | 
																			
																				| Auxiliary earth electrode resistance (RH) | Max 100 kΩ | 
																			
																				| Additional error from RH and RS | RH[kΩ]•••RS[kΩ]/RA[Ω]•••0.2 % | 
																			
																				| Monitoring of RS and RH with error indicator. Automatic range selection.
 | 
																			
																				| RA 3-Pole Selective Ground Resistance Measurement with Current Clamp (RA with Clamp ) | 
																			
																				| Switch position | RA 3-pole with clamp | 
																			
																				| Resolution | 0.001 Ω to 10 Ω | 
																			
																				| Measuring range | 0.020 Ω to 19.99 kΩ | 
																			
																				| Accuracy | ± (7 % rdg + 3 d) | 
																			
																				| Operating error | ± (10 % rdg + 5 d) | 
																			
																				| 
																						Measuring Principle: Current/Voltage Measurement (with External Current Clamp) | 
																			
																				| Measuring voltage | Vm = 48 V ac | 
																			
																				| Short-circuit current | > 50 mA | 
																			
																				| Measure frequency | 128 Hz | 
																			
																				| Probe resistance (RS) | Max 100 kΩ | 
																			
																				| Auxiliary earth electrode resistance (RH) | Max 100 kΩ | 
																			
																				| Monitoring of RS and RH with error indicator. Automatic range selection.
 Measurement is not performed if the current through the current clamp is too low.
 | 
																			
																				| RA 4-Pole Selective Ground Resistance Measurement with Current Clamp (RA with Clamp ) | 
																			
																				| Switch position | RA 4-pole with clamp | 
																			
																				| Resolution | 0.001 Ω to 10 Ω | 
																			
																				| Measuring range | 0.020 Ω to 19.99 kΩ | 
																			
																				| Accuracy | ± (7 % rdg + 3 d) | 
																			
																				| Operating error | ± (10 % rdg + 5 d) | 
																			
																				| Measuring Principle: Current/Voltage Measurement (with External Current Clamp) | 
																			
																				| Measuring voltage | Vm = 48 V ac | 
																			
																				| Short-circuit current | > 50 mA | 
																			
																				| Measure frequency | 128 Hz | 
																			
																				| Probe resistance (RS) | Max 100 kΩ | 
																			
																				| Auxiliary earth electrode resistance (RH) | Max 100 kΩ | 
																			
																				| Monitoring of RS and RH with error indicator. Automatic range selection.
 Measurement is not performed if the current through the current clamp is too low.
 | 
																			
																				| Stakeless Ground Loop Measurement (2 Clamps ) | 
																			
																				| Switch position | RA 4-pole 2 clamps | 
																			
																				| Resolution | 0.001 Ω to 10 Ω | 
																			
																				| Measuring range | 0.020 Ω to 19.99 kΩ | 
																			
																				| Accuracy | ± (7 % rdg + 3 d) | 
																			
																				| Operating error | ± (10 % rdg + 5 d) | 
																			
																				| Measuring Principle: Stakeless Measurement of Resistance in Closed Loops Using Two Current Transformers | 
																			
																				| Measuring voltage | Vm = 48 V ac | 
																			
																				| Measure frequency | 128 Hz | 
																			
																				| Noise current (IEXT) | Max. IEXT = 10 A (ac) (RA < 20 Ω) | 
																			
																				| Max. IEXT = 2 A (ac) (RA > 20 Ω) | 
																			
																				| Automatic range selection. The information regarding stakeless ground loop measurements is only valid when used in conjunction with the recommended current clamps at the minimum distance specified.
 |