Gas Detection Solution for Safety Compliance
| Refrigerants | 1,000 ppm | 
| CO2 | 5,000 / 10,000 / 20,000 / 30,000 / 40,000 / 50,000 ppm | 
| NH3 | 100 / 1,000 / 5,000 ppm / 100% LEL | 
| O2 | 30 Vol% | 
| CO | 500 / 1,000 ppm | 
| Combustible Gases - Semiconductor (R-290, R-600, CH4, R-600a, HC-12a, R-717) | 5,000 ppm | 
| Combustible Gases - Catalytics R-600, CH4, R-290, NH3 | 100% LEL | 
| NO2 | 20 ppm | 
	
	Ambient Conditions
| Temperature | Semiconductor | -40 to 122 °F / -40 to 50 °C | 
| Electrochemical | NH3 100 / 1,000 ppm: -40 to 40 °C | |
| NH3 5,000 ppm: -20 to 40 °C | ||
| CO 500 ppm: -40 to 50 °C | ||
| NO2 20 ppm: -20 to 40 °C | ||
| O2 30% Volume: -20 to 50 °C | ||
| Humidity | 5 to 90% RH, non-condensing | |
| Pressure | 23.6 to 32.5 inch Hg / 800 to 1,100 mbar | |
	
	Technical Specifications
| Status Indicator | Tri-color LED (green, red, orange) | 
| Buzzer | 72dB @ 10 cm | 
| Approvals | CE, UL / CSA / IEC EN 61010-1 | 
Malaysia