Applicable for oil-free system (T series)
 Smaller installation space: low height, small volume, lightweight
 Optimized flow path design for noise reduction
 Fast operation, Energy Saving
 Applicable for reversible systems like heat pumps: bidirectional flow
 Applicable refrigerants: R22, R134A, R404A, R407C, R410A etc.
 Cooling Capacity: 3,5 to 105 kW (R22 Nominal Capacity)
 Medium temperature: -30°C (-22°F) to +70°C (158°F) (duty cycle rate below 50%)
 Ambient temperature: -30°C (-22°F) to +60°C (140°F) (duty cycle rate below 50%)
 Relative humidity: below 95% RH
 Ps: 4.5MPa (45 Bar)
 Installation position: Coil upwards, valve rotor central axis within +/-15° versus vertical axis
 500 steps (full stroke); 32 ± 20 opening steps
 Rated Voltage: 12V DC(+/- 10%), rectangular wave
 Actuating mode: 4-phase 8-step permanent magnet stepping motor of the direct-acting type
 Excitation mode: 1 ~ 2 phase excitation, monopole actuation
 Excitation rate: 30 to 90pps (Maintain excitation in stop position min. 0.1~1.0sec. to activate the self-holding mechanism.)
 Coil current: 260mA/phase (20°C)
 Coil resistance: 46 +/- 3.7 ?/phase (20°C)
 Insulation class of coil: E
 Protection class: IP 66