important instructions regarding the type/s of protection of the motors.
		
		
			
				Main features
			
				ELPROM Ex electric motors are manufactured and tested in compliance w ith all the EN/IEC standards and also in campiance w ith the main
			
				European Directives. First of all the directive 94/9/EC (ATEX as already explained), 2004/108/EC (EMC Electro Magnetic Compatibility),
			
				2006/42/EC (Machinery Directive), 2002/95/EC (RoHS).
			
				ATEX characteristics:
			
				·  Suitable for Surface plants different from mines (Group II)
			
				·  Presence of Gas: Zone 1 and Zone 2
			
				·  Type of protection ‘Ex d’ or ‘Ex de’
			
				·  Gas group IIC, IIB and IIA
			
				·  Temperature class T3, T4 E T5 (suitable also for T2, T1)
			
				·  Ambient temperature range -40°C +60°C for temper ature class T3
			
				-40°C +60°C for temperature class T4
			
				-40°C +40°C for temperature class T5
			
				·  Presence of DUST: Zone 21 and Zone 22
			
				·  Type of protection Ex tD A21 IP66 (IP65 for Ex de)
			
				·  Surface Temperature T125°C
			
				·  Ambient temperature range -40°C +50°C
			
				All the motors are asynchronous with squirrel cage rotor, wound stator, closed and externally ventilated in compliance w ith EN 60034-6 (IC 411).
			
				The supply voltages allow ed can exceed the nominal value of ±5%.
			
				All the electrical and mechanical features and the testing methods comply w ith the standard EN 60034-1.
			
				The power ratings and the dimensions of the motors comply w ith EN 50347 and IEC 60072-1, the mounting arrangements B3, B5, B14
			
				comply w ith EN 60034-7.
			
				All the geometrical dimensions are unified according to the tables UNEL 13113-71; 13117-71; 13118- 7; IEC 60072-1.
			
				The IP degrees of protection of the motors comply with EN 60034-5 and EN 60259.
			
				Insulation class. All the motors have an insulation class F in compliance w ith EN 60034-1. Insulation class H on request.
			
				The bearings are high-quality single raw deep grooves ball bearings, preloaded by a wave spring.
			
				Duty. The motors are normally made for S1 duty; otherw ise intermittent duties can be provided on request after performing the heating tests.
			
				Single-phase motors: Capacitor placed in a safe Ex d cylindrical box fitted to the motor.
			
				Windings:
			
				Made using enamelled copper wires are insulated w ith two layers (insulation class H). They are painted w ith another layer of varnish and after
			
				this placed in an oven for the drying process.
			
				It is also possible to tropicalize the windings using special additional varnish with high hygroscopic characteristics so to be used in places w ith
			
				an humidity >60% (see options)
			
				Rotors
			
				Die-cast aluminium squirrel cage or aluminium alloy (Al-Si Silumin).
			
				The shafts of the motors and the keys-shaft comply IEC 60072-1. Special shaft are made on request (see options).
			
				Frame (in compliance w ith EN 50347)
			
				Die-cast aluminium w ith high mechanical strength, with a good thermal conductivity and light weight.
			
				The feet can be mounted on the motor frame in 3 different positions, in the bottom or on right and left side.
			
				Terminal box
			
				The terminal box in case of motor B3, is normally on the top of the motor. As the feet are removable also on the sides of the frame it is possible
			
				to have the terminal box on both sides of the motor too.
			
				Flanges and shields (in compliance w ith EN 503471)
			
				Die-cast aluminium, w ith dimensions as per standard IEC 60072-1, or w ith special shapes on request:
			
				The motor is completely modular so that the flanges can be mounted or removed depending on the needs w ithout affecting the Ex type of
			
				protection (as the flange are mounted on the front shield).
			
				Ventilation (in compliance with EN 60034-6)
			
				Self-ventilated motors IC 411. Depending on the type of protection the fan can be in plastic or in aluminium.
			
				Ex d, Ex de Plastic fan
			
				Ex tD A21 Antistatic plastic or aluminium fan
			
				Fan cover
			
				Zinc-plated steel sheet.
			
				Noise (in compliance w ith EN 60034-9)
				
				
					3.4 Main Options
				
					Axially locked shaft
				
					Motors w ith a locked bearing on the font shield using an elastic metal ring. This solution is necessary in case of alternative axial stress (ie. Bevel
				
					gear pinion w ith alternative load or motion, frequent start-up under load or with high inertia) so to create axial movement of the shaft and bumps
				
					on the bearings.
				
					Low temperatures motors (-40 °C)
				
					They have to be fitted w ith special bearing, metallic fan, metallic cable gland and plugs or made with special plastic materials.
				
					In these cases, if there is a risk of condensation, it is better to fit the motors w ith “anti-condensation heaters”.
				
					Anti-condensation Heaters
				
					For motors installed in cold and w et places, with significant temperature ranges, moisture condensation can be dangerous for the resistance of
				
					the w inding insulation. Upon request, we can apply appropriate heaters directly on the heads of winding.
				
					The terminals are connected to a terminal board inside the connection box of the motor.
				
					The heaters are available at 110V and 220 V , w ith a tolerance of +/- 10%
				
					Tropicalization of windings
				
					If the motors are installed outdoors or in high humidity areas, the windings may be tropicalized w ith a special varnish with high hygroscopic
				
					characteristics in order to protect the insulation materials by the condensation. This protection avoid the reduction of the insulation properties of
				
					the w indings.
				
					Inverter duty motors
				
					All these motors can be driven by a converter. In this case they must be fitted with thermal protections inside the w indings.
				
					Special voltages and frequencies
				
					The standard three phase motors are produced at the follow ing nominal voltages and frequencies:
				
					230 / 400 V , 50 Hz
				
					The motors can run at a different nominal voltage w ith a tolerance of +/- 5%
				
					On customer request, we can produce motors w ith special voltage and frequency.
				
					Special shafts
				
					On customer request, it is possible to supply motors with special shaft (according to the customer draw ing). It is necessary to send the draw ing
				
					to our Technical Department for a feasibility study.
				
					It is possible to supply motors with shaft of different material from the standard ( C40 ), using Stainless Steel or others, w ith standard or special
				
					dimensions.
				
					Special flanges
				
					Due to the modular flange assembling is possible to have, on request special flanges.
				
					Rain fan cover
				
					For outdoor applications, vertical mounting, DE shaft down ( V5, V1, V18 ) it is suggested to assemble a special cowl with a rain cover. It is
				
					available for all the frame sizes.
				
					Thermistors (PTC Positive Temperature Coefficient)
				
					They must be used in case of motors driven by inverters.
				
					They are fitted inside the windings in number of 3 with a series connection to be connected to an appropriate tripping device that cut off the
				
					motors supply in case the winding reach the thermal probe limit temperature.
				
					On request will be available protectors with different temperature setting in respect of the maximum Temperature class or surface temperature
				
					of the motor.
				
					Thermal cut-off (bimetallic probes)
				
					Motors w ith 1 or 2 thermal protectors w ith normally closed contact in series connection into the winding.
				
					The series of contact shall be connected to an appropriate tripping device that cut off the motors supply in case the winding reaches the thermal
				
					probe limit temperature.
				
					On request will be available protectors with different temperature setting in respect of the maximum Temperature class or surface temperature
				
					of the motor.
				
					PT100
				
					It is a device that increase its resistance according with the increasing of the temperature.
				
					It is useful for continuous measuring of the w inding temperature, properly connected to an electronic equipment.
				
					Single-phase motor with balanced winding - BIPHASE
				
					They have normally a starting torque higher than the standard 1-phase and can start easily without using a start capacitor.
				
					Painting (against corrosion)
				
					The Elprom motors have diecasted aluminium components and sandblasted. If it is not requested the motors are supplied unpainted.
				
					On specific request and for batches not less than 30 pcs. , it is possible to have motors with epoxy paint, w ith the customer requested colour.
				
					Other paints with anti salt characteristics are available on request; contact our Technical Department.