| Item | Data | |||
| APPROVAL | / | |||
| Test standard | IEC60947-7-1 | |||
| Pitch [mm] | 12.2 | |||
| Poles | 01P | |||
| IEC60947 Test data | / | |||
| Rated voltage [V] | 400 | |||
| Rated current [A] | 6 | |||
| Rated connection capacity(solid/stranded) [mm²] | 0.2~6 | |||
| Surge voltage category/pollution degree/material group | III/2/I | |||
| Rated impulse voltage [KV] | 4 | |||
| Rated torque [N.m] | 0.5 | |||
| UL1059Test data | UL 1059 | |||
| Use group | B | C | D | |
| Rated voltage [V] | 300 | / | / | |
| Rated current [A] | 10 | / | / | |
| Rated connection capacity (solid/stranded) [AWG] | 30~10 | |||
| Rated torque [Lb. in] | 4.43 | |||
| General data | / | |||
| Screw | M3 | |||
| Inflammability class UL94 | V0 | |||
| Ambient temperature [℃] | -40~+105 | |||
| Relative humidity | 5%-95% | |||
| Inspection standard | MIL-STD-105E II | |||
| AQL | 0.65 | |||
| Warranty | 12 months | |||
| Material and plating | / | |||
| Housing | PA66 | |||
| Screw | Copper alloy,Ni plated | |||
| Contact | Copper alloy,Sn plated | |||
| Cage | Copper alloy,Ni plated | |||
| Current carrier | Copper alloy,Sn plated | |||
| Wire connecting | ||||
| Recommended stripping length 8mm; | ||||
| 1.For solid wire, stripping wire to the appointed length, then tightening with rated torque. | ||||
| 2.For stranded wire: stripping wire to the appointed length, mating with corresponding type of ferrule, then tightening with rated torque. | ||||