|
Comet T3511 Specifications |
|
Technical parameters |
Value |
|
Output |
Ethernet |
|
Measured Value |
Temperature + Relative Humidity |
|
Construction Type |
With T+RH Probe on Cable |
|
Design |
Industrial |
|
Temperature Measuring Range |
-30 to 105 °C |
|
Relay Output |
No |
|
Two-State Input |
No |
|
Lcd Display |
Yes |
|
PoE |
No |
|
Relative humidity range |
0 to 100% |
|
Accuracy of relative humidity measurement |
±2.5% relative humidity from 5 to 95% at 23°C |
|
Accuracy of temperature output |
±0.4°C |
|
Resolution |
0.1°C, 0.1%RH |
|
Measuring interval |
2s |
|
Available temperature units |
degrees Celsius, degrees Fahrenheit |
|
Computed values |
dew point, absolute humidity, specific humidity, mixing ratio, specific enthalpy |
|
Accuracy and range of dew point temperature output - for more details see graphs in manual |
±1.5°C at ambient temperature lower than 25°C and RH>30% range -60 to +80°C |
|
Range of humidity sensor temperature compensation |
all temperature range |
|
Temperature operating range of case with electronics |
-30 to +80°C |
|
IP protection |
IP30 electronics, IP40 sensors |
|
LAN connection |
RJ-45 connector, 10Base-T or 100Base-TX |
|
Communication protocols |
WWW, ModbusTCP, SNMPv1, SOAP, XML |
|
Alarm protocols |
E-mail, SNMP Trap, Syslog |
|
Configuration |
T-Sensor, WWW configuration |
|
Filtering ability of sensor cover |
0.025mm - filter with stainless steel mesh |
|
Power |
9 to 30Vdc, maximum consumption 1W |
|
Power connector |
co-axial, diameter 5.5 x 2.1mm |
|
Length of the probe cable |
1m, 2m or 4m optionally |
|
Dimensions |
display unit 88.5 x 93 x 39.5mm (W x H x D), probe length 88mm, probe diameter 18mm |
|
Weight |
approximately 210g - 1m probe |