| Technical data | KL1809 |
|---|---|
| Connection technology | 1-wire |
| Specification | EN 61131-2, type 1/3 |
| Number of inputs | 16 |
| Nominal voltage | 24 V DC (-15%/+20%) |
| “0” signal voltage | -3…+5 V (EN 61131-2, type 1/3) |
| “1” signal voltage | 11…30 V (EN 61131-2, type 3) |
| Input filter | typ. 3 ms |
| Input current | typ. 3 mA (EN 61131-2, type 3) |
| Current consumption K-bus | typ. 20 mA |
| Current consumption power contacts | typ. 4 mA + load |
| Electrical isolation | 500 V (K-bus/field potential) |
| Bit width in the process image | 16 inputs |
| Configuration | no address or configuration setting |
| Weight | approx. 60 g |
| Storage temperature | -40…+85°C |
| Operating temperature | -25…+60°C |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP20/variable (see documentation) |
| Approvals/markings | CE, CCC, UL, ATEX, IECEx, DNV |
| Ex marking |
ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc |