| Features | Descriptions |
| Physical Features | |
| Dimensions | 48 mm x 48 mm 86,5 mm |
| Protection Class | IP65 at front, IP20 at rear |
| Installation | Fixed Installation |
| Storage / Operating Temperature | 0°C...50°C |
| Storage / Operating Humidity | 90 % max. (None condensing) |
| Electrical Features | |
| Supply Voltage and Power | 100-240Vac 50/60Hz 115Vac (±%15) 50/60Hz 230Vac (±%15) 50/60Hz 24Vac/dc (±%15) 50/60Hz 24Vac (±%15) 50/60Hz 10-30Vdc |
| Sensor Inputs | TC, RTDThermocouple (TC): J, K, R, S veT(IEC584.1)(ITS90) thermoresistance(RTD) PT-100 (IEC751)(ITS90) |
| Optional Sensor Inputs | |
| Scale | Fe CuNi -200°C,900°C NiCr Ni -200°C,1300°C Pt13%Rh 0°C,1700°C Pt10%Rh 0°C,1700°C Cu CuNi -200°C,400°C PT 100 -200°C,650°C PT 100 -199.9°C,650.0°C |
| Accuracy | Thermocouple (TC):( ± 0.25% of full scale or ± 3ºC, which one is greater) ±1 digit max. Thermoresistance (RTD):( ± 0.25% of full scale or ± 2ºC, which one is greater) ±1 digit |
| Output | |
| Relay Output | Relay (5A@250Vac at Resistive Load) Relay (5A@250V ac at Resistive Load) (Alarm Output) |
| SSR Output | Maximum 10 mA @ 12 Vdc |
| Analogue Output | |
| Optional Outputs | |
| Control | |
| Control Form | Programmable On / Off, P, PI, PD, and PID |
| Reading Frequency | 10 readings per second |
| Communication Protocols | |
| Approvals | CE |