Response spectrum range: 4.3μm, 5.0μm, 185~260nm
The longest detection distance can reach 50 meters
Multi-level sensitivity settings to meet the needs of different occasions
Magnetic bar adjusts sensitivity, no need opening the cover on site
FD10-UVIR2 flame detector uses two IR sensors and one UV ultraviolet sensor. Infrared sensors are with different wavelengths with narrow-band filtering. Ultraviolet sensor is with solar-blind band. One IR sensor and the UV sensor are used to reflect the center wavelength of the flame information. The other IR sensor is used to monitor other infrared radiation in the environment. Combining with the flicker characteristics of the flame, analyzing through high-speed microprocessors and calculating by mathematical algorithms, the radiation spectrum with flame characteristics is confirmed as a fire alarm.
The detector suppress the interference of sunlight, lightning, electric welding, thermal radiation, electromagnetic interference, mechanical vibration and other interference, thus achieving the rapid response and accurate identification of the flame signal.
Using high-speed, low-consumption and high-performance 32-bit data processing chip
Excellent resistance to radio frequency and electromagnetic interference
Perfect patent algorithm, fast response, high stability, strong anti-false alarm ability
Detection angle of 90° (IR sensors) and 120° (UV sensor)
The longest detection distance can reach 50 meters
Multi-level sensitivity settings to meet the needs of different occasions
Magnetic bar adjusts sensitivity, no need opening the cover on site
Explosion-proof design, suitable for hazardous areas in many types of industrial sites
Heavy industry applications, tunnel industry, oil and gas tank farm, power industry and petrochemical industry, etc.
| Response spectrum range | 4.3μm, 5.0μm, 185~260nm |
| Detection object | Flame |
| Detection method | Real-time sampling of optical path |
| Display method | LED lights |
| Status indication | Green LED flashes to indicate normal operation (the number of flashes every 3 seconds represents the sensitivity level) Red LED always lights to indicate an alarm |
| Operation method | Magnetic bar to adjust sensitivity (4 levels totally) |
| Signal output | 4-20mA output 2 relays for fault and alarm (free contact) |
| Response time | <30s |
| Ex grade | Ex d IIC T6 Gb / Ex tD A21 |
| Ingress protection | IP66 |
| Supply voltage | DC24V±6V |
| Working current | ≤30mA (DC23V) |
| Longest detection distance | 50 meters, 0.3m×0.3m N-heptane fire |
| Field of view | IR sensors: 90° UV sensor: 120° |
| Weight | 1.5±0.2kg |
| Installation method | Wall mounted or lifting or holding-pipe |
| Cable entry interface | NPT1/2, default transfer to G1/2 (internal thread) |
| Housing material | Copper-free cast aluminum (epoxy resin on the surface) |
| Environment temp | -20℃~+60℃ |
| Environment humidity | ≤95%RH (no condensation) |
Malaysia