| product type designation |
CM 1243-5 |
| Technical Product Detail Page |
https://i.siemens.com/1P6GK7243-5DX30-0XE0 |
| transfer rate |
| transfer rate |
|
| ● at the 1st interface / according to PROFIBUS |
9.6 kbit/s ... 12 Mbit/s |
| interfaces |
| number of interfaces / according to Industrial Ethernet |
0 |
| number of electrical connections |
|
| ● at the 1st interface / according to PROFIBUS |
1 |
| ● for power supply |
1 |
| type of electrical connection |
|
| ● at the 1st interface / according to PROFIBUS |
9-pin Sub-D socket (RS485) |
| ● for power supply |
3-pole terminal block |
| supply voltage, current consumption, power loss |
| type of voltage / of the supply voltage |
DC |
| supply voltage / external |
24 V |
| supply voltage / external / at DC / rated value |
24 V |
| relative positive tolerance / at DC / at 24 V |
20 % |
| relative negative tolerance / at DC / at 24 V |
20 % |
| consumed current |
|
| ● from external supply voltage / at DC / at 24 V / typical |
0.1 A |
| power loss [W] |
2.4 W |
| ambient conditions |
| ambient temperature |
|
| ● for vertical installation / during operation |
0 ... 45 °C |
| ● for horizontally arranged busbars / during operation |
0 ... 55 °C |
| ● during storage |
-40 ... +70 °C |
| ● during transport |
-40 ... +70 °C |
| relative humidity |
|
| ● at 25 °C / without condensation / during operation / maximum |
95 % |
| protection class IP |
IP20 |
| design, dimensions and weights |
| module format |
Compact module S7-1200 single width |
| width |
30 mm |
| height |
100 mm |
| depth |
75 mm |
| net weight |
0.134 kg |
| fastening method |
|
| ● 35 mm DIN-rail mounting |
Yes |
| ● S7-300 rail mounting |
No |
| ● wall mounting |
Yes |
| product features, product functions, product components / general |
| number of units |
|
| ● per CPU / maximum |
3 |
| performance data / PROFIBUS DP |
| service / as DP master |
|
| ● DPV1 |
Yes |
| number of DP slaves |
|
| ● on DP master / operable |
32 |
| data volume |
|
| ● of the address range of the inputs / as DP master / total |
512 byte |
| ● of the address range of the outputs / as DP master / total |
512 byte |
| ● of the address range of the inputs / per DP slave |
244 byte |
| ● of the address range of the outputs / per DP slave |
244 byte |
| ● of the address range of the diagnostic data / per DP slave |
240 byte |
| service / as DP slave |
|
| ● DPV0 |
No |
| ● DPV1 |
No |
| performance data / S7 communication |
| number of possible connections / for S7 communication |
|
| ● maximum |
8; max. 4 connections to other S7 stations |
| ● with PG connections / maximum |
1 |
| ● with PG/OP connections / maximum |
3 |
| performance data / multi-protocol mode |
| number of active connections / with multi-protocol mode |
|
| ● without DP / maximum |
8 |
| ● with DP / maximum |
8 |
| performance data / telecontrol |
| protocol / is supported |
|
| ● TCP/IP |
No |
| product functions / management, configuration, engineering |
| configuration software |
|
| ● required |
STEP 7 Basic/Professional |
| product function / is supported / identification link |
Yes; acc. to IEC 61406-1:2022 |
| standards, specifications, approvals |
| reference code |
|
| ● according to IEC 81346-2:2019 |
KEC |
| certificate of suitability / CE marking |
Yes |
| certificate of suitability / UKCA marking |
Yes |
| certificate of suitability / KC approval |
Yes |
| certificate of suitability / Regulatory Compliance Mark (RCM) |
Yes |
| certificate of suitability / RoHS conformity |
Yes |
| certificate of suitability / EAC approval |
Yes |
| standards, specifications, approvals / hazardous environments / header |
| certificate of suitability / ATEX |
Yes |
| certificate of suitability / IECEx |
Yes |
| certificate of suitability / CCC / for hazardous zone according to GB standard |
Yes |
| certificate of suitability / FM registration |
Yes |
| standards, specifications, approvals / marine classification / header |
| Marine classification association / American Bureau of Shipping Europe Ltd. (ABS) |
Yes |
| Marine classification association / French marine classification society (BV) |
Yes |
| Marine classification association / Det Norske Veritas (DNV) |
Yes |
| Marine classification association / Lloyds Register of Shipping (LRS) |
Yes |
| Marine classification association / Nippon Kaiji Kyokai (NK) |
Yes |
| Marine classification association / Royal Institution of Naval Architects (RINA) |
Yes |
| standards, specifications, approvals / Environmental Product Declaration |
| Environmental Product Declaration |
Yes |
| global warming potential [CO2 eq] |
|
| ● total |
89.58 kg |
| ● during manufacturing |
14.29 kg |
| ● during operation |
75.11 kg |
| ● after end of life |
0.18 kg |