| General information |
| Product type designation |
DI 4x120 ... 230 V AC ST |
| HW functional status |
from FS04 |
| Firmware version |
V0.0 |
| ● FW update possible |
No |
| usable BaseUnits |
BU type B1 |
| Color code for module-specific color identification plate |
CC41 |
| Product function |
| ● I&M data |
Yes; I&M0 to I&M3 |
| ● Isochronous mode |
No |
| ● suitable for operation on PROFINET R1 IMs |
Yes |
| Engineering with |
| ● STEP 7 TIA Portal configurable/integrated from version |
V14 |
| ● STEP 7 configurable/integrated from version |
V5.5 SP3 |
| ● PROFIBUS from GSD version/GSD revision |
One GSD file each, Revision 3 and 5 and higher |
| ● PROFINET from GSD version/GSD revision |
GSDML V2.3 |
| Operating mode |
| ● DI |
Yes |
| ● Counter |
No |
| ● Oversampling |
No |
| ● MSI |
No |
| Supply voltage |
| Rated value (AC) |
230 V |
| permissible range, upper limit (AC) |
264 V |
| Reverse polarity protection |
No |
| Input current |
| Current consumption (rated value) |
10 mA |
| Encoder supply |
| Number of outputs |
4 |
| Short-circuit protection |
No; when using BU type B1, a fuse with 10 A tripping current must be provided |
| Output current |
| ● up to 60 °C, max. |
10 A |
| Power loss |
| Power loss, typ. |
1 W; Active power, load voltage 230 V, all inputs connected with 230 V, 50 Hz |
| Address area |
| Address space per module |
| ● Address space per module, max. |
1 byte; + 1 byte for QI information |
| Hardware configuration |
| Automatic encoding |
Yes |
| ● Mechanical coding element |
Yes |
| ● Type of mechanical coding element |
type C |
| Selection of BaseUnit for connection variants |
| ● 1-wire connection |
BU type B1 |
| ● 2-wire connection |
BU type B1 |
| ● 3-wire connection |
BU type B1 |
| ● 4-wire connection |
BU type B1 + potential distributor module |
| Digital inputs |
| Number of digital inputs |
4 |
| Digital inputs, parameterizable |
Yes |
| Source/sink input |
P-reading |
| Input characteristic curve in accordance with IEC 61131, type 3 |
Yes |
| Input voltage |
| ● Rated value (AC) |
230 V |
| ● for signal "0" |
0V AC to 40V AC |
| ● for signal "1" |
74 V AC to 264 V AC |
| Input current |
| ● for signal "1", typ. |
10.8 mA |
| Input delay (for rated value of input voltage) |
| for standard inputs |
| — parameterizable |
No |
| — at "0" to "1", min. |
1.5 ms |
| — at "0" to "1", max. |
4 ms |
| — at "1" to "0", min. |
10 ms |
| — at "1" to "0", max. |
10 ms |
| Cable length |
| ● shielded, max. |
1 000 m |
| ● unshielded, max. |
600 m |
| Encoder |
| Connectable encoders |
| ● 2-wire sensor |
Yes |
| Interrupts/diagnostics/status information |
| Alarms |
| ● Diagnostic alarm |
No |
| ● Maintenance interrupt |
No |
| ● Hardware interrupt |
No |
| Diagnoses |
| ● Monitoring the supply voltage |
No |
| ● Wire-break |
No |
| ● Short-circuit |
No |
| Diagnostics indication LED |
| ● Monitoring of the supply voltage (PWR-LED) |
Yes; green PWR LED |
| ● Channel status display |
Yes; green LED |
| ● for channel diagnostics |
No |
| ● for module diagnostics |
Yes; green/red DIAG LED |
| Potential separation |
| Potential separation channels |
| ● between the channels |
No |
| ● between the channels and backplane bus |
Yes |
| ● between the channels and the power supply of the electronics |
No |
| Isolation |
| Isolation tested with |
2 545 V DC/2 s (routine test) |
| Standards, approvals, certificates |
| Suitable for safety functions |
No |
| Ecological footprint |
| ● environmental product declaration |
Yes |
| Global warming potential |
| — global warming potential, (total) [CO2 eq] |
15.9 kg |
| — global warming potential, (during production) [CO2 eq] |
3.69 kg |
| — global warming potential, (during operation) [CO2 eq] |
12.7 kg |
| — global warming potential, (after end of life cycle) [CO2 eq] |
-0.495 kg |
| Ambient conditions |
| Ambient temperature during operation |
| ● horizontal installation, min. |
-30 °C |
| ● horizontal installation, max. |
60 °C |
| ● vertical installation, min. |
-30 °C |
| ● vertical installation, max. |
50 °C |
| Altitude during operation relating to sea level |
| ● Installation altitude above sea level, max. |
2 000 m; On request: Installation altitudes greater than 2 000 m |
| Dimensions |
| Width |
20 mm |
| Height |
73 mm |
| Depth |
58 mm |
| Weights |
| Weight, approx. |
36 g |