product brand name |
SIRIUS |
product designation |
Circuit breaker |
design of the product |
For motor protection |
product type designation |
3RV1 |
General technical data |
size of the circuit-breaker |
S00 |
size of contactor can be combined company-specific |
S00 |
product extension auxiliary switch |
Yes |
power loss [W] for rated value of the current |
|
● at AC in hot operating state |
7.25 W |
● at AC in hot operating state per pole |
2.4 W |
insulation voltage with degree of pollution 3 at AC rated value |
690 V |
surge voltage resistance rated value |
6 kV |
mechanical service life (operating cycles) |
|
● of the main contacts typical |
100 000 |
● of auxiliary contacts typical |
100 000 |
electrical endurance (operating cycles) typical |
100 000 |
reference code according to IEC 81346-2 |
Q |
Substance Prohibitance (Date) |
01/01/2013 |
SVHC substance name |
Lead - 7439-92-1 |
Weight |
0.288 kg |
Ambient conditions |
installation altitude at height above sea level maximum |
2 000 m |
ambient temperature |
|
● during operation |
-20 ... +60 °C |
● during storage |
-50 ... +80 °C |
● during transport |
-50 ... +80 °C |
relative humidity during operation |
10 ... 95 % |
Main circuit |
number of poles for main current circuit |
3 |
adjustable current response value current of the current-dependent overload release |
2.8 ... 4 A |
type of voltage for main current circuit |
AC |
operating voltage |
|
● rated value |
20 ... 690 V |
● at AC-3 rated value maximum |
690 V |
● at AC-3e rated value maximum |
690 V |
operating frequency rated value |
50 ... 60 Hz |
operational current rated value |
4 A |
operational current |
|
● at AC-3 at 400 V rated value |
4 A |
● at AC-3e at 400 V rated value |
4 A |
operating power |
|
● at AC-3 |
|
— at 230 V rated value |
0.75 kW |
— at 400 V rated value |
1.5 kW |
— at 500 V rated value |
2.2 kW |
— at 690 V rated value |
3 kW |
● at AC-3e |
|
— at 230 V rated value |
0.75 kW |
— at 400 V rated value |
1.5 kW |
— at 500 V rated value |
2.2 kW |
— at 690 V rated value |
3 kW |
operating frequency |
|
● at AC-3 maximum |
15 1/h |
● at AC-3e maximum |
15 1/h |
Auxiliary circuit |
design of the auxiliary switch |
transverse |
type of voltage for auxiliary and control circuit |
AC/DC |
number of NC contacts for auxiliary contacts |
1 |
number of NO contacts for auxiliary contacts |
1 |
number of CO contacts for auxiliary contacts |
0 |
operational current of auxiliary contacts at AC-15 |
|
● at 24 V |
2 A |
● at 110 V |
2 A |
● at 120 V |
2 A |
● at 125 V |
2 A |
● at 230 V |
0.5 A |
operational current of auxiliary contacts at DC-13 |
|
● at 24 V |
1 A |
● at 60 V |
0.15 A |
Protective and monitoring functions |
product function |
|
● ground fault detection |
No |
● phase failure detection |
Yes |
trip class |
CLASS 10 |
design of the overload release |
thermal |
maximum short-circuit current breaking capacity (Icu) |
|
● at AC at 240 V rated value |
100 kA |
● at AC at 400 V rated value |
100 kA |
● at AC at 500 V rated value |
3 kA |
● at AC at 690 V rated value |
2 kA |
operating short-circuit current breaking capacity (Ics) at AC |
|
● at 240 V rated value |
100 kA |
● at 400 V rated value |
100 kA |
● at 500 V rated value |
3 kA |
● at 690 V rated value |
2 kA |
response value current of instantaneous short-circuit trip unit |
52 A |
UL/CSA ratings |
full-load current (FLA) for 3-phase AC motor |
|
● at 480 V rated value |
4 A |
● at 600 V rated value |
4 A |
yielded mechanical performance [hp] |
|
● for single-phase AC motor |
|
— at 110/120 V rated value |
0.13 hp |
— at 230 V rated value |
0.33 hp |
● for 3-phase AC motor |
|
— at 200/208 V rated value |
0.8 hp |
— at 220/230 V rated value |
0.75 hp |
— at 460/480 V rated value |
2 hp |
— at 575/600 V rated value |
3 hp |
contact rating of auxiliary contacts according to UL |
C300 / R300 |
Short-circuit protection |
product function short circuit protection |
Yes |
design of the short-circuit trip |
magnetic |
design of the fuse link |
|
● for short-circuit protection of the auxiliary switch required |
fuse gG: 10 A, miniature circuit breaker C 6 A (short-circuit current Ik < 400 A) |
design of the fuse link for IT network for short-circuit protection of the main circuit |
|
● at 240 V |
none required |
● at 400 V |
gG 40 A |
● at 500 V |
gG 35 A |
● at 690 V |
gG 35 A |
Installation/ mounting/ dimensions |
mounting position |
any |
fastening method |
screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715 |
height |
90 mm |
width |
45 mm |
depth |
75 mm |
required spacing |
|
● for grounded parts at 400 V |
|
— downwards |
20 mm |
— upwards |
20 mm |
— at the side |
9 mm |
● for live parts at 400 V |
|
— downwards |
20 mm |
— upwards |
20 mm |
— at the side |
9 mm |
● for grounded parts at 500 V |
|
— downwards |
20 mm |
— upwards |
20 mm |
— at the side |
9 mm |
● for live parts at 500 V |
|
— downwards |
20 mm |
— upwards |
20 mm |
— at the side |
9 mm |
● for grounded parts at 690 V |
|
— downwards |
20 mm |
— upwards |
20 mm |
— backwards |
0 mm |
— at the side |
9 mm |
— forwards |
0 mm |
● for live parts at 690 V |
|
— downwards |
20 mm |
— upwards |
20 mm |
— backwards |
0 mm |
— at the side |
9 mm |
— forwards |
0 mm |
Connections/ Terminals |
type of electrical connection |
|
● for main current circuit |
screw-type terminals |
● for auxiliary and control circuit |
screw-type terminals |
arrangement of electrical connectors for main current circuit |
Top and bottom |
type of connectable conductor cross-sections |
|
● for main contacts |
|
— solid or stranded |
2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), 2x (1 ... 4 mm²) |
— finely stranded with core end processing |
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²) |
type of connectable conductor cross-sections |
|
● for auxiliary contacts |
|
— solid or stranded |
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²) |
tightening torque |
|
● for main contacts with screw-type terminals |
0.8 ... 1.2 N·m |
● for auxiliary contacts with screw-type terminals |
0.8 ... 1.2 N·m |
design of screwdriver shaft |
Diameter 5 to 6 mm |
size of the screwdriver tip |
Pozidriv size 2 |
design of the thread of the connection screw |
|
● for main contacts |
M3 |
● of the auxiliary and control contacts |
M3 |
Safety related data |
product function suitable for safety function |
Yes |
suitability for use |
|
● safety-related switching on |
No |
● safety-related switching OFF |
Yes |
service life maximum |
10 a |
test wear-related service life necessary |
Yes |
proportion of dangerous failures |
|
● with low demand rate according to SN 31920 |
40 % |
● with high demand rate according to SN 31920 |
50 % |
B10 value with high demand rate according to SN 31920 |
5 000 |
failure rate [FIT] with low demand rate according to SN 31920 |
50 FIT |
ISO 13849 |
device type according to ISO 13849-1 |
3 |
overdimensioning according to ISO 13849-2 necessary |
Yes |
IEC 61508 |
safety device type according to IEC 61508-2 |
Type A |
Electrical Safety |
protection class IP on the front according to IEC 60529 |
IP20 |
touch protection on the front according to IEC 60529 |
finger-safe, for vertical contact from the front |
Display |
display version for switching status |
Rocker switch |