The RM Series 60-600kVA Modular Online UPS features an innovative new topology with a bidirectional DC-DC converter circuit, significantly enhancing system performance and ensuring high efficiency. Its compact design delivers exceptional power density, with the 600kW system occupying just 0.9m² of space. The RM Series offers an ideal power supply solution for large data centers and critical facilities.
High Efficiency: Up to 97%
Lithium Battery Support
Intelligent Staggered Power Consumption: Enhanced flexibility and energy savings
Double-Sided DC-DC Topology: Supports charging power up to 30%
High Power Density
Battery Neutral-Free Design: Supports various battery configurations and horizontal DC voltages
User-Friendly Interface: 10" touch color LCD with graphic display for intuitive operation
Modular Design: Supports up to 30 power modules in parallel, hot-swappable with N+X redundancy
The RM Series includes a bypass and monitoring module equipped with intelligent slots, communication interfaces, battery cold start buttons, and ample dry contacts. These features ensure convenient data transfer and comprehensive system monitoring:
Multiple communication interfaces including RS485, USB, CAN, and programmable dry contacts
Convenient SD card slot for easy software updates and version upgrades in maintenance mode
Isolation between the LCD and monitoring board connected via network cable to improve reliability and protect DSP components
The RM600/60D cabinet houses 10 power modules, each delivering 60kVA in a compact 2U height. With front panel knobs, these modules support hot-swapping without power interruption, enabling online redundancy and maintenance:
Compact modular cabinet design with up to 10 slots
Module status LEDs for real-time power module condition monitoring
Bidirectional DC-DC converter supporting 30% charging power, enhancing system performance
Overall efficiency up to 97%, with optimized battery and power grid collaboration for maximum UPS utilization
Model | RM600/60D | |||||
System Capacity | 600kVA | |||||
Power Module Capacity | 60kVA/kW | |||||
Input | Dual Input | Standard | ||||
Phase | 3Phase+Neutral+Ground, 380/400/415VAC (line-line) | |||||
Rate Frequency | 50/60Hz | |||||
Input Voltage Range | 323~478Vac (line-line),full load 323V~138Vac (line-line), load decrease linearly from 100% to 40% according to the min phase voltage |
|||||
Input Frequency Range | 40Hz~70Hz | |||||
Inpput PF | >0.99 | |||||
Input THDi | <3% (100% Linear load) | |||||
Bypass | Rate Voltage | 380/400/415VAC (line-line) | ||||
Rate Frequency | 50/60Hz | |||||
Input Voltage Range | Settable, default -20%~+15% Up limit: +10%, +15%, +20%, +25% Down limit: -10%, -15%, -20%, -30%, -40% |
|||||
Bypass Frequency Range | Settable, ±1Hz, ±3Hz, ±5Hz | |||||
Bypass Overload | 110% for long term operation; 110%~125% for 5 mins; 125%~150% for 1 min; 150%~400% for 1 s; >400% less than 200ms |
|||||
Output | Rate Voltage | 380/400/415VAC (line-line) | ||||
Rate Frequency | 50/60Hz | |||||
Output PF | 1 | |||||
Voltage Regulation | ±1% | |||||
Output THDu | <1% Linear load; <5%, Non-linear load | |||||
Inverter Overload | <110%, 1hour; 110%~125%, 10mins; 125%~150%, 1min; >150%, 200ms |
|||||
Rate Frequency | 50/60Hz | |||||
Frequency Precision | ± 0.1% | |||||
Battery | Voltage | ±180~288VDC 30~32pcs derate to 0.7; 34~36pcs derate to 0.8; 38pcs derate to 0.9; 40~48pcs |
||||
Voltage Precision | 0.01 | |||||
Charge Power | Up to 30% * Output active power | |||||
System | Efficiency | AC Mode | >97% | |||
Battery Mode | >96% | |||||
Display | LED+Color touch LCD | |||||
Interface | Standard: RS485, USB, CAN, Programmable Dry Contact | |||||
Option | SNMP card, AS400 card, Parallel kit, SPD, Dual input kit, LBS, Common battery kit | |||||
Temperature | Operation: 0~40 ℃ Storage: -40~70 ℃ | |||||
Relative Humidity | 0~95% Non-condensing | |||||
Noise(1 meter) | 75dB @ 100% load, 70dB @ 45% load | |||||
Altitude | <1000m. Within 1000m~2000m, 1% power derating for every 100m | |||||
Application Standard | Safety: IEC/EN 62040-1 EMC: IEC/EN 62040-2 Performance: IEC/EN 62040-3 | |||||
Physical | Dimension (W*D*H,mm) | Cabinet | 800*1100*2000 | |||
Power Module | 550*750*85 | |||||
Weight (kg) | Cabinet | 443 | ||||
Power Module | 35.7 |