20–200kVA (380V/400V/415V)
The RM Series Modular Online UPS is a highly reliable solution designed for small to medium-sized data centers. As the first-generation UPS from INVT Power, this system is available in 60kVA, 120kVA, and 200kVA capacities. Its modular IGBT architecture and isolated air channels enable outstanding adaptability to harsh environments.
Supports up to 20 hot-swappable power modules in parallel, enabling true online N+X redundancy.
Delivers up to 200kVA within a compact 0.53 footprint, optimizing valuable data center space.
Each power module includes an independent charger, intelligently managing the full charging cycle to extend battery lifespan.
All IGBT components are integrated within a single module, reducing failure points and enhancing system performance and reliability.
The UPS can start directly from battery power even without a utility power source.
Equipped with a touch-screen LCD that provides comprehensive and intuitive system information.
Supports both top and bottom cable entry, making installation more convenient and accessible.
Tracks operational time of key components and provides timely reminders for maintenance or replacements.
Modular UPS configurations up to 60kVA are available with built-in isolation transformers, catering to diverse customer requirements.
Capacity | 20-200KVA | |||||||||
Main Input | ||||||||||
Input voltage | 304~478Vac (line-line), full load; 228V~304Vac (line-line), load decreases linearly according to the min phase voltage |
|||||||||
Input frequency | 50/60Hz | |||||||||
Power factor | >0.99 | |||||||||
Input voltage window | -40%~+25%,-10%~-40% rated power derating from 100%~50% | |||||||||
Frequency window | 40-70HZ | |||||||||
Battery | ||||||||||
Battery voltage | ±240VDC | |||||||||
Charger power | 20%*Active Power | |||||||||
Charger voltage precision | 1% | |||||||||
Bypass | ||||||||||
Bypass voltage | 380V/400V/415V, line to line 220V/230V/240V, line to neutral |
|||||||||
Bypass voltage window | -20%-+15%, full load | |||||||||
Bypass overload capabiltiy | 125%, long time operation | |||||||||
125%< load <130%, last for more than 1 hour | ||||||||||
130%<load<150%,last for more than 6 minutes | ||||||||||
>1000%, last for more than 100ms | ||||||||||
Output | ||||||||||
Output voltage | 380V/400V/415V, line to line | |||||||||
Voltage precision | 1% (balance load),1.5% (unbalance load) | |||||||||
Voltage THD(Total Harmonic Distortion) | THD<1.5%(linear load),THD<7%(nonlinear load) | |||||||||
Power factor | 0.9 | |||||||||
Phase tolerance | 120°±0.5° (balance and unalance load) | |||||||||
Crest factor | 3:1 | |||||||||
Overload capabiltiy | 105% transfer to bypass after 30 minutes | |||||||||
110%, transfer to bypass after 10minutes | ||||||||||
125%, transfer to bypass after 1 minutes | ||||||||||
150%, transfer to bypass after 30 seconds | ||||||||||
>150%, transfer to bypass after 200ms | ||||||||||
System | ||||||||||
System efficiency | Normal mode: 94.5%@60~70% load | |||||||||
ECO mode: 98% | ||||||||||
Battery mode efficiency | 94.5%@60~70% load | |||||||||
Display | LCD+LED, Touch screen and keyboard | |||||||||
IP class | IP20 | |||||||||
Interface (Communication Ports ) | RS232,RS485,Dry contacts,SNMP card,EPO,Generator interface | |||||||||
Installation/Connection | Top or bottom cable connection | |||||||||
Operation temperature | 0-40 | |||||||||
Storage temperature | -25~70 | |||||||||
Relative humidity | 0-95% (non-comdensing) | |||||||||
Noise(dB) | <55dB | |||||||||
Weight(KG) | 3-module cabinet | RM060/20 | 171KG | |||||||
6-module cabinet | RM120/20 | 277KG | ||||||||
10-module cabinet | RM200/20 | 399KG | ||||||||
PM20 | 20KVA: 22KG | |||||||||
Dimension(W*D*H)(mm) | 3-module cabinet | 600*900*1100 | ||||||||
6-module cabinet | 600*900*1600 | |||||||||
10-module cabinet | 600*900*2000 | |||||||||
Module | 440*590*134 | |||||||||
*Products specifications are subject to change without further notice. |