Technical Data
| Measurement functions | Measurement range | Display range | Resolution | Accuracy |
|---|---|---|---|---|
| Voltage | 0 V…750 V | 0 V…750 V | 1 V | ±(2% m.v. + 2 digits) |
| Frequency | 45.0 Hz…65.0 Hz | 45.0 Hz…65.0 Hz | 0.1 Hz | ±(0.1% m.v. + 1 digit) |
| Short-circuit loop parameters | ||||
| 4p method - high current measurement maximum current 300 A | 7.2 mΩ…1999 mΩ acc. to EN 61557 | 0.0 mΩ…1999 mΩ | from 0.1 mΩ | ±(2% m.v. + 2 mΩ) |
| 2p method - standard current measurement maximum current 37 A | from 0.13 Ω…199.9 Ω acc. to EN 61557 | 0.00 Ω…199.9 Ω | from 0.01 Ω | from ±(2% m.v. + 3 digits) |
| Short-circuit current readings | ||||
| 4p method - high current measurement network voltage 115 V…690 V | up to 57.5 A…95.8 kA acc. | 115.0 A…690 kA | from 0.1 A | Calculated on the basis of error for fault loop |
| 2p method - standard current measurement | from 2.00 A…3.21 kA acc. to EN 61557 | 1.150 A…40.0 kA | from 0.001 A | Calculated on the basis of error for fault loop |
| Touch and shock voltage | ||||
| 4p method - high current measurement | 0 V…100 V | 0 V…100 V | 1 V | ±(10% m.v. + 2 digits) |
m.v. - measured value
Weight and dimensions| Parameter | Value |
|---|---|
| Net weight (kg) | 5.3 |
| Package weight (kg) | 10.5 |
| Package width (cm) | 49 |
| Package height (cm) | 42 |
| Package length (cm) | 35 |