| Item | Specifications |
|---|---|
| Insulation resistance | 20 MΩ min. between AC external terminals and GR terminal at 500 VDC, *1.) |
| Dielectric strength | 2,300 VAC, 50/60 Hz between AC external terminals and GR terminal for 1 min, leakage current: 10 mA max. *1 *3 |
| 720 VAC, 50/60 Hz between DC external terminals and GR terminal for 1 min, leakage current: 10 mA max. *1 |
|
| Noise immunity | Conforms to IEC61000-4-4, 2 kV (power line) |
| Vibration resistance | Conforms to JIS C0040 Amplitude: 0.075 mm (10 to 57 Hz), Acceleration: 9.8 m/s2 (57 to 150 Hz) for 80 min in X, Y, and Z directions (10 sweeps of 8 min = 80 min total) |
| Shock resistance | Conforms to JIS C0041 147 m/s2 3 times each in X, Y, and Z directions |
| Ambient operating temperature |
0 to 55 °C |
| Ambient operating humidity |
10% to 90% (with no condensation) |
| Atmosphere | No corrosive gases |
| Ambient storage temperature |
- 20 to 75 °C |
| Ground | Less than 100 Ω |
| Structure | For installation in a control panel |
| Dimensions (mm) | 49 × 90 × 80 mm (W × H × D) excluding cable |
| Weight | 5 kg max. per Module |
| Safety standards | EC, C-Tick, UL approval pending *4 |