| Wiring connections | 1P2W, 1P3W, 3P3W, 3P4W | 
				
					| Measurements and parameters
 | Voltage, Current, Frequency, Active power, Reactive power, Apparent power, Power factor(cosθ), Phase angle,
 Harmonics(THD-R/THD-F), Phase rotation
 | 
				
					| AC Voltage | 
				
					|  | 
				
					| Range | 1000V | 
				
					| Accuracy | ±0.7%rdg±3dgt (40.0~70.0Hz) ±0.3%rdg±5dgt (70.1~1KHz)
 | 
				
					| Crest factor | 1.7 or less | 
				
					| AC Current | 
				
					|  | 
				
					| Range | 40.00/400.0/1000A (Auto-ranging) | 
				
					| Accuracy | ±1.0%rdg±3dgt (40.0~70.0Hz) ±2.0%rdg±5dgt (70.1~1kHz)
 | 
				
					| Crest factor | 3 or less on 40.00A/400.0A range, 3 or less 1500A peak on 1000A range
 | 
				
					| Frequency | 
				
					|  | 
				
					| Display range | 40.0~999.9Hz | 
				
					| Accuracy | ±0.3%rdg±3dgt | 
				
					| Active power | 
				
					|  | 
				
					| Range | 40.00/400.0/1000kW (Auto-ranging) | 
				
					| Accuracy | ±1.7%rdg±5dgt (PF1, sine wave, 45~65Hz) influence of phase angle within ±3.0°
 | 
				
					| Apparent power | 
				
					|  | 
				
					| Range | 40.00/400.0/1000kVA (Auto-ranging) | 
				
					| Reactive power | 
				
					|  | 
				
					| Range | 40.00/400.0/1000kVar (Auto-ranging) | 
				
					| Power factor | 
				
					|  | 
				
					| Display range | -1.000~0.000~1.000 | 
				
					| Phase angle(1P2W only) | 
				
					|  | 
				
					| Display range | 180.0~0.0~+179.9 | 
				
					| Harmonics RMS *Content rate | 
				
					|  | 
				
					| Analysis order | 1st~30th order | 
				
					| Effective frequency | 50/60Hz | 
				
					| Accuracy | ±5.0%rdg±10dgt (1~10th) ±10%rdg±10dgt (11~20th)
 ±20%rdg±10dgt (21~30th)
 | 
				
					| Harmonics THD-R/THD-F | 
				
					|  | 
				
					| Display range | 0.0%~100.0% | 
				
					| Accuracy | ±1 against the calculated results of each measured value | 
				
					| Phase rotation | ACV 80~1100V (45~65Hz) | 
				
					| Other functions | MAX/MIN/AVG/PEAK, Data hold, Back light, Auto power off | 
				
					| General | 
				
					|  | 
				
					| Communication interface
 | Bluetooth®5.0, Android™5.0 or more, iOS 10.0 or more ※1
 | 
				
					| Power source | LR6 (AA) (1.5V) ×2 | 
				
					| Continuous measuring time
 | Approx. 58 hours | 
				
					| Conductor size | φ75 mm (max) and busbar of 80 × 30 mm or less | 
				
					| Dimensions / Weight | 283(L) × 143(W) × 50(D) mm / Approx. 590g (including batteries) | 
				
					| Applicable Standards | IEC 61010-1, IEC 61010-2-032 (main unit) / IEC 61010-031 (test leads)
 CAT IV 600 V / CAT III 1000 V Pollution degree 2,
 IEC 61326 (EMC) Class B, EN50581 (RoHS), EN 301 489-1,
 EN 300 328, EN 62479, IEC 60529 (IP40)
 | 
				
					| Included Accessories | 7290 (Test leads) 9198 (Soft Case)
 LR6(AA)×2, Instruction Manual
 |