NF802 is the new generation of digital relay test equipment with local control. This digital relay tester is equipped with 8 optical ports, and its powerful data processing capability can achieve the full functional test of the IEC61850 devices. Support GPS\ IRIG-B\ IEEE 1588 synchronization, it makes the substation internal debugging and substation to substation combine debugging available. NF802 integrated some unique functions including: the abnormal SVGOOSE simulation, virtual terminal test, the optical power testing and so on.
| The main power | |
|---|---|
| Rated voltage | 220V (AC) |
| Allowable range | 100V~240V (AC) |
| Rated frequency | 50Hz |
| Allowable frequency | 40~60Hz |
| Current | 1A(max) |
| Ethernet communication port: for communication with the PC | |
| Type | 10/100Base-TX (10/100Mbit, twisted-pair, automatic cross) |
| Front panel fiber-optic communication interface: for IEC61850-9-1/2, GOOSE communication | |
| Number of port | 8 |
| Interface type | LC |
| Front panel FT3 interface: for IEC60044-7/8 of FT3 communication | |
| Standard | IEC60044-7/8 |
| Number of port | 8 |
| Interface type | ST |
| Low –level Signal Analog Output | |
| Signal amplitude | |
| Output channel | 12 |
| Set range | AC:0~7.07Vrms DC:0~10V |
| Accuracy |
0.07~7.07Vrms : < 0.2% 0.02~0.07Vrms : < 1% |
| Frequency | |
| Sinusoidal signal | 10~1000Hz |
| Transient signal | DC~10.0kHz |
| Accuracy | 0.002%(under frequency,error 1mHz) |
| Resolution | 0.001Hz |
| Phase | |
| Range of phase angle | 0 to 359. 9° |
| Accuracy | <0.1°,50/60Hz |
| Resolution | ±0.01° |
| 8 pairs of binary input(A-H) | |
| Input characteristic | 30V~250V (DC)or empty contact (automatic identification) |
| Sample frequency | 10kHz |
| Time resolution | 100us |
| 4 pairs of binary output(1-4) | |
| Type | Empty contacts, regardless of polarity |
| AC capacity | Vmax :250V(AC)/Imax :0.5A |
| DC capacity | Vmax :250V(DC)/Imax :0.5A |
| 4 pairs of binary output(5-8) | |
| Type | Fast contact output, the speed of response is 100us |
| AC capacity | Vmax :220V(AC)/Imax :0.5A |
| DC capacity | Vmax :220V(AC)/Imax :0.5A |
Malaysia