Circutor CVM-A1600 Power Quality Analyzer
| Item | Brief Description |
| Product name | Circutor CVM-A1600 Power Quality Analyzer |
| Model in datasheet | CVM-A1610-ITF |
| Code | M57110 |
| Main positioning | Class A power quality analyzer for supply quality monitoring, PQ event recording, waveform capture, and standards-based reporting. |
| Primary standards | IEC 61000-4-30 Ed.3, IEC 62586-2, IEC 61000-4-7, IEC 61000-4-15, IEC 61557-12, IEC 62053-22, IEC 62053-24, EN 50160 reporting referenced in Circutor article. |
| Typical customer applications | Main incomer / utility supply boundary, critical distribution boards, high-consumption loads, industrial plants, commercial facilities and facilities with VFDs, UPS, chargers or power electronics. |
| Integration message | Integrates with Energy Management Systems via REST API, Modbus TCP and IEC 61850; also supports RS-485 Modbus RTU and Ethernet protocols. |
| Feature | Webpage explanation / customer value |
| Class A power quality analyzer | Provides standardised and reliable measurement data according to IEC 61000-4-30 Ed.3 and IEC 62586-2 methods. |
| PQ event recording | Captures voltage and current disturbances such as dips, overvoltages, interruptions and transients. |
| Waveform capture | Stores event waveforms to support root-cause investigation and discussions with utilities or internal maintenance teams. |
| Harmonics and interharmonics | Analyses harmonics and interharmonics up to the 63rd order for identifying distortion caused by VFDs, UPS, chargers and power electronics. |
| Flicker and imbalance monitoring | Measures flicker, voltage/current unbalance and THD/TDD to evaluate network quality and equipment stress. |
| 8-inch touchscreen | Simplifies local operation and helps users view live values, histories and events without specialist software. |
| Built-in web server | Allows remote access to instantaneous values, historical data and device configuration. |
| EN 50160 reporting | Automatically generates power quality reports against EN 50160 limits, with conclusions that can be emailed or sent to remote servers. |
| EMS / cloud integration | Supports APIRest, Modbus TCP, IEC 61850, RS-485 Modbus RTU, HTTPS, NTP, DNS, WSS, SFTP, FTP and SMTP. |
| Multi-site readiness | Can be connected to Circutor Scout platform / Quality Analyst module for centralised quality monitoring across multiple installations. |
| Parameter | Specification |
| Product / model | CVM-A1610-ITF, Code M57110 |
| Certification | IEC 61000-4-30 |
| Power supply | 100...300 Vac/Vdc |
| AC supply frequency | 47...63 Hz |
| AC consumption | 14...20 VA |
| DC consumption | 8.5...9 W |
| Auxiliary battery autonomy | 20 s |
| Input current | .../5 A | .../1 A | 250 mA |
| Communications | Ethernet | RS-485 | Wi-Fi |
| Serial communication | RS-485, Modbus RTU |
| Network interface | 2 x Ethernet 10BaseT / 100BaseTx, RJ45 |
| Network protocols | HTTPS, NTP, DNS, WSS, SFTP, FTP, IEC 61850, SMTP, Modbus TCP |
| Display | 8-inch touchscreen |
| Mounting | Panel mounting, DIN 43700 cut-out 138 x 138 mm |
| Size | 201 x 145 x 131 mm |
| Weight | 0.95 kg |
| Protection | IP40 front, IP30 unmounted |
| Working temperature | -20...+65 °C |
| Storage temperature | -20...+80 °C |
| Relative humidity | 5...95%, without condensation |
| Circuit / Parameter | Specification |
| Voltage nominal range | 110...480 V Ph-N, 190...830 V Ph-Ph |
| Voltage measuring range | 10...600 V~ Ph-N |
| Frequency measuring range | 42.5...69 Hz |
| Input impedance | 2 MOhm |
| Minimum measurement voltage | 10 V Ph-N, 17 V Ph-Ph |
| Voltage circuit installation category | CAT III 600 V (2000 m), CAT III 300 V (5000 m) |
| Current nominal input | .../5 A for IEC 61000-4-30, .../1 A, .../0.250 A |
| Phase current measuring range | 0.01...6 A (.../5 A) IEC 61000-4-30; 0.01...12 A (.../1 A); 0.01...0.3 A (.../0.250 A) |
| Neutral current measuring range | 0.01...6 A (.../5 A); 0.01...12 A (.../1 A); 0.01...0.3 A (.../0.250 A) |
| Maximum pulse current | 15 A (.../5 A) |
| Minimum current measurement | 0.01 A |
| Maximum input current consumption | 0.9 VA |
| Current circuit installation category | CAT III 600 V (2000 m), CAT III 300 V (5000 m) |
| Measurement | Accuracy / Class |
| Phase voltage | +/- 0.1% Un (class 0.1) (10%...150%), Class A IEC 61000-4-30 |
| Neutral voltage | +/- 0.1% Un (class 0.1) (10%...150%) |
| Phase current | 0.2% (0.01...10 A) (.../5 A), Class A IEC 61000-4-30 |
| Neutral current | 0.2% (0.01...10 A) (.../5 A) |
| Frequency | Class 0.02 (42.5...69 Hz), +/- 10 mHz IEC 61000-4-30 |
| Active power | Class 0.2 +/- 1 digit IEC 61557-12 |
| Reactive power | Class 0.5 +/- 1 digit IEC 61557-12 |
| Active energy | Class 0.2S IEC 62053-22 |
| Reactive energy | Class 0.5S IEC 62053-24 |
| Power factor | Class 0.5 IEC 61557-12 |
| Voltage THD | Class A IEC 61000-4-30 and Class I IEC 61000-4-7 (0.2%...100%) |
| Current THD | Class A IEC 61000-4-30 and Class I IEC 61000-4-7 (0.2%...100%) |
| Voltage harmonics (THD) | Class A IEC 61000-4-30 and Class I IEC 61000-4-7, +/- 0.15% (0.08%...200%) |
| Flicker Pinst / Pst | Class A IEC 61000-4-30 and Class F1 IEC 61000-4-15 (0...10 Pst) |
| Voltage unbalance Kd | Class A IEC 61000-4-30, +/- 0.15% (0%...200%) |
| Current unbalance Kd | Class A IEC 61000-4-30, +/- 0.15% (0%...200%) |
| Code | Type | Power supply | Input current | Transistor outputs | Relays | Digital inputs | Communications |
| M57110 | CVM-A1610-ITF | 100...300 Vac/Vdc | .../5 A | .../1 A | 250 mA | 0 | 0 | 0 | Ethernet | RS-485 | Wi-Fi |
| M57111 | CVM-A1611-ITF | 100...300 Vac/Vdc | .../5 A | .../1 A | 250 mA | 6 | 2 | 6 | Ethernet | RS-485 | Wi-Fi |
| M57112 | CVM-A1612-ITF | 100...300 Vac/Vdc | .../5 A | .../1 A | 250 mA | 12 | 4 | 12 | Ethernet | RS-485 | Wi-Fi |
| Customer issue | Relevant CVM-A1600 capability | Webpage angle |
| Unexplained production stoppages or machine trips | Records dips, swells, interruptions and transients with waveforms. | Identify whether disturbances are supply-related or internally generated. |
| Need to prove supply quality to utility or management | Class A IEC 61000-4-30 measurements and automatic EN 50160 reports. | Use standardised evidence rather than assumptions. |
| Sensitive PLCs, automation and control systems | Detects voltage variations, disturbances, flicker and harmonic distortion. | Reduce nuisance faults and unexpected resets. |
| Harmonics from VFDs, UPS, chargers or power electronics | Harmonics and interharmonics analysis up to the 63rd order. | Locate distortion sources and prioritise mitigation. |
| Multi-site PQ monitoring | Connectivity with EMS, Scout platform / Quality Analyst and remote protocols. | Centralise PQ data, events and alarms across plants or buildings. |
| Limited in-house PQ expertise | 8-inch touchscreen, web server and automatic reports. | Make power quality information easier for maintenance teams to interpret. |


Malaysia