Technical data
Power supply
Supply voltage : 85 ... 265 V AC/110 ... 125 V DC or 10 ... 30 V AC/10 ... 42 V DC
Frequency AC : 40 ... 400 Hz
Power consumption : max. 2.2 W, max. 3.3 VA
Working temperature : -10 ... +60 °C (14 ... 140 °F)
Isolation voltage : 500 V AC according to VDE 0110 Gr. 2
between input/output/supply voltage
Test voltage : 4 kV DC between input/output/supply voltage
-conformity : EN55022, IEC61000-4-4/5/11/13, EN60555-2
Input
Sensor current : Pt100 approx. 1 mA, Pt1000 approx. 0.25 mA (no self-heating)
Cable resistance : max. 100 Ω (operation with safety barriers possible)
automatic compensation of cable resistance at 3-wire configuration
Offset adjust : Pt100 approx. +/-8 Ω, (×20°C), Pt1000 approx. +/-8 Ω (× 2°C)
(to compensate cable resistance at 2-wire configuration)
Span : adjustable ca. +/-5 %
Broken or shorted line : output rises to max. value
Output
Current output : 0 ... 20 mA, 4 ... 20 mA switch selectable, max. 1 kΩ burden
Voltage output : 0 ... 10 V, 2 ... 10 V switch selectable,
max. 15 mA load, short circuit proof
(simultaneous to current output max. 5 mA)
Accuracy : ≤ 0.2 % (≤ 0.1 % factory calibration for one range available)
Temperature coefficient : ≤ 0.01 %/K
Current and voltage putput : ≤ 0.1 %
Case
: standard case of polycarbonate 8020 UL94V-1
Weight : ca. 200 g
Connection : screw-terminals with pressure plates, max. 2.5 mm²
Protection : case IP40, terminals IP20, finger safe acc. German BGV A3