Model |
G9SE-401 |
|
Operating time (OFF to ON state) *2 |
100 ms Max. *3 |
|
Response time (ON to OFF state) *4 |
15 ms Max. |
|
Accuracy of OFF-delay time |
- |
|
Inputs |
Input current |
5 mA Min. |
|
ON voltage |
11 VDC Min. |
|
OFF voltage |
5 VDC Max. |
|
OFF current |
1 mA Max. |
|
Maximum cable length |
100 m Max. |
|
Reset input time |
250 ms Min. |
Contact
outputs |
Contact resistance *5 |
100 mΩ |
|
Mechanical durability |
5,000,000 operations Min. |
|
Electrical durability |
50,000 operations Min. |
Switching specification Inductive
load (IEC/EN60947-5-1) |
AC15: 240 VAC 2 A
DC13: 24 VDC 1.5 A |
|
Minimum applicable load |
24 VDC 4 mA |
Conditional short-circuit current
(IEC/EN60947-5-1) |
100 A *6 |
|
Pollution degree |
2 |
|
Over voltage category (IEC/EN60664-1) |
Safety output: Class III, the others: Class II |
Insulation
specification |
Isolation voltage (Ui) |
250 VAC |
Impulse
withstand
voltage
(IEC/
EN60947-5-1) |
Between input and
output |
6 kV |
Between different
poles of output |
6 kV (between 13-14/23-24 and 33-34/43-44 (37-38/47-48))
4 kV (between 13-14 and 23-24, between 33-34 (37-38) and
43-44 (47-48)) |
Dielectric
strength |
Between input and
output |
2,200 VDC |
Between different
poles of output |
1,500 VAC |
|
Insulation resistance |
100 MΩ |
|
Vibration resistance *7 |
Frequency: 10 to 55 to 10 Hz
Amplitude: 0.35 mm half amplitude (0.7 mm double amplitude) |
Mechanical
shock re-
sistance *7 |
Destruction |
300 m/s2 |
|
Malfunction |
100 m/s2 |
|
Surrounding Air Temperature |
-10 to 55°C (No freezing or condensation) |
|
Ambient humidity |
25% to 85%RH |
|
Degree of protection |
IP20 |
|
Weight |
approx. 180 g |