Response spectrum range: 3.8μm, 4.3μm, 5.0μm
Response time: <30s
Ingress protection: IP66
Supply voltage: DC24V±6V
The longest detection distance can reach 50 meters
FD10-IR3 triple IR flame detector is a new type of intelligent fire detection equipment. The detectors uses 3 infrared sensors with different wavelengths with narrow-band filtering. One sensor is used to reflect the center wavelength of the flame information. The other two sensors is used to monitor other infrared radiation in the environment. Combining with the flicker characteristics of the flame, analyzing through high-speed microprocessors and calculating by mathematical algorithms, the radiation spectrum with flame characteristics is confirmed as a fire alarm.
The detector suppress the interference of sunlight, lightning, electric welding, thermal radiation, electromagnetic interference, mechanical vibration and other interference, thus achieving the rapid response and accurate identification of the flame signal.
Using high-speed, low-consumption and high-performance 32-bit data processing chip
Excellent resistance to radio frequency and electromagnetic interference
Perfect patent algorithm, fast response, high stability, strong anti-false alarm ability
Detection angle of 90°
The longest detection distance can reach 50 meters
Multi-level sensitivity settings to meet the needs of different occasions
Magnetic bar adjusts sensitivity, no need opening the cover on site
Explosion-proof design, suitable for hazardous areas in many types of industrial sites
Hart output (optional)
Heavy industry applications, tunnel industry, oil and gas tank farm, power industry and petrochemical industry, etc.
| Response spectrum range | 3.8μm, 4.3μm, 5.0μm |
| Detection object | Flame |
| Detection method | Real-time sampling of optical path |
| Display method | LED lights |
| Status indication | Green LED flashes to indicate normal operation (the number of flashes every 3 seconds represents the sensitivity level) Red LED always lights to indicate an alarm |
| Operation method | Magnetic bar to adjust sensitivity (4 levels totally) |
| Signal output | 4-20mA (optional Hart) 2 relays for fault and alarm (free contact) |
| Response time | <30s |
| Ex grade | Ex d IIC T6 Gb / Ex tD A21 |
| Ingress protection | IP66 |
| Supply voltage | DC24V±6V |
| Working current | ≤30mA (DC23V) |
| Longest detection distance | 50 meters, 0.3m×0.3m N-heptane fire |
| Detection angle | 90° |
| Weight | 1.5 / 4.5kg |
| Installation method | Wall mounted or lifting or holding-pipe |
| Cable entry interface | NPT1/2, default transfer to G1/2 (internal thread) |
| Housing material | Aluminum Stainless steel |
| Environment temp | -20℃~+60℃ |
| Environment humidity | ≤95%RH (no condensation) |