| General information | ||
| Product type designation | IM 155-5 PN BA | |
| HW functional status | From FS02 | |
| Firmware version | V4.3.0 | |
| ● FW update possible | Yes | |
| Vendor identification (VendorID) | 0x002A | |
| Device identifier (DeviceID) | 0X0312 | |
| Product function | ||
| ● I&M data | Yes; I&M0 to I&M3 | |
| ● Module swapping during operation (hot swapping) | No | |
| ● Isochronous mode | No | |
| ● IRT | No | |
| ● Tool changer | No | |
| ● Local coupling, IO data | No | |
| Engineering with | ||
| ● STEP 7 TIA Portal configurable/integrated from version | V15.1 | |
| ● STEP 7 configurable/integrated from version | use GSD file | |
| ● PROFINET from GSD version/GSD revision | GSDML V2.3 | |
| Configuration control | ||
| via dataset | No | |
| Supply voltage | ||
| Rated value (DC) | 24 V | |
| permissible range, lower limit (DC) | 19.2 V | |
| permissible range, upper limit (DC) | 28.8 V | |
| Reverse polarity protection | Yes | |
| Short-circuit protection | Yes | |
| Mains buffering | ||
| ● Mains/voltage failure stored energy time | 5 ms | |
| Input current | ||
| Current consumption (rated value) | 1 A; at 24 V DC and without load | |
| Current consumption, max. | 1.7 A | |
| Inrush current, max. | 2.8 A | |
| I²t | 0.04 A²·s | |
| Power | ||
| Infeed power to the backplane bus | 14 W | |
| Power loss | ||
| Power loss, typ. | 3 W | |
| Address area | ||
| Address space per module | ||
| ● Address space per module, max. | 64 byte; For input and output data respectively | |
| Address space per station | ||
| ● Address space per station, max. | 64 byte; For input and output data respectively | |
| Hardware configuration | ||
| Integrated power supply | Yes; 14 W | |
| System power supply can be plugged in to left of IM | No | |
| Number of permissible power segments | 1; incl. interface module | |
| Rack | ||
| ● Modules per rack, max. | 12; I/O modules | |
| Submodules | ||
| ● Number of submodules per station, max. | 108; 9 per I/O module | |
| Interfaces | ||
| Number of PROFINET interfaces | 1; 2 ports (switch) | |
| 1. Interface | ||
| Interface types | ||
| ● RJ 45 (Ethernet) | Yes | |
| ● Number of ports | 2 | |
| ● integrated switch | Yes | |
| ● BusAdapter (PROFINET) | No | |
| Protocols | ||
| ● PROFINET IO Device | Yes | |
| ● Open IE communication | Yes | |
| ● Media redundancy | Yes; PROFINET MRP client | |
| PROFINET IO Device | ||
| Services | ||
| — IRT | No | |
| — PROFIenergy | No | |
| — Prioritized startup | No | |
| — Shared device | Yes | |
| — Number of IO Controllers with shared device, max. | 2 | |
| Interface types | ||
| RJ 45 (Ethernet) | ||
| ● Transmission procedure | PROFINET with 100 Mbit/s full duplex (100BASE-TX) | |
| ● 100 Mbps | Yes | |
| ● Autonegotiation | Yes | |
| ● Autocrossing | Yes | |
| Protocols | ||
| Supports protocol for PROFINET IO | Yes | |
| PROFIsafe | Yes; FW V4.3.0 or higher | |
| PROFIBUS | No | |
| EtherNet/IP | No | |
| Modbus TCP | No | |
| Redundancy mode | ||
| ● PROFINET system redundancy (S2) | No | |
| — on S7-1500R/H | No | |
| — on S7-400H | No | |
| ● PROFINET system redundancy (R1) | No | |
| ● H-Sync forwarding | No | |
| Media redundancy | ||
| — MRP | Yes | |
| — MRPD | No | |
| Open IE communication | ||
| ● TCP/IP | Yes | |
| ● SNMP | Yes | |
| ● LLDP | Yes | |
| Interrupts/diagnostics/status information | ||
| Status indicator | Yes | |
| Alarms | Yes | |
| Diagnostics function | Yes | |
| Diagnostics indication LED | ||
| ● RUN LED | Yes; green LED | |
| ● ERROR LED | Yes; red LED | |
| ● MAINT LED | Yes; Yellow LED | |
| ● Connection display LINK TX/RX | Yes; 2x green-yellow LEDs | |
| Potential separation | ||
| between backplane bus and electronics | No | |
| between PROFINET and all other circuits | Yes; 1500 V AC (type test) | |
| between supply and all other circuits | No | |
| Permissible potential difference | ||
| between different circuits | Safety extra low voltage SELV | |
| Isolation | ||
| Isolation tested with | 707 V DC (type test) | |
| Standards, approvals, certificates | ||
| Siemens Eco Profile (SEP) | Siemens EcoTech | |
| Network loading class | 2 | |
| Ecological footprint | ||
| ● environmental product declaration | Yes | |
| Global warming potential | ||
| — global warming potential, (total) [CO2 eq] | 64.1 kg | |
| — global warming potential, (during production) [CO2 eq] | 11.1 kg | |
| — global warming potential, (during operation) [CO2 eq] | 53.6 kg | |
| — global warming potential, (after end of life cycle) [CO2 eq] | -0.669 kg | |
| Ambient conditions | ||
| Ambient temperature during operation | ||
| ● horizontal installation, min. | -30 °C; From FS03 | |
| ● horizontal installation, max. | 60 °C | |
| ● vertical installation, min. | -30 °C; From FS03 | |
| ● vertical installation, max. | 40 °C | |
| Altitude during operation relating to sea level | ||
| ● Installation altitude above sea level, max. | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual | |
| Dimensions | ||
| Width | 35 mm | |
| Height | 147 mm | |
| Depth | 129 mm | |
| Weights | ||
| Weight, approx. | 236 g | |