SITOP PSU300S 40 A stabilized power supply input: 400-500 V 3 AC output: 24 V DC/40 A

SITOP PSU300S 40 A stabilized power supply input: 400-500 V 3 AC output: 24 V DC/40 A

Category: SIEMENS Simatic Control Systems Available
For more information, visit our official website at geasb.com

Description

input
type of the power supply network 3-phase AC
supply voltage at AC  
● minimum rated value 400 V
● maximum rated value 500 V
● initial value 340 V
● full-scale value 550 V
wide range input Yes
buffering time for rated value of the output current in the event of power failure minimum 6 ms
operating condition of the mains buffering at Vin = 400 V
line frequency 50/60 Hz
line frequency 47 ... 63 Hz
input current  
● at rated input voltage 400 V 2 A
● at rated input voltage 500 V 1.7 A
current limitation of inrush current at 25 °C maximum 60 A
I2t value maximum 3.4 A²·s
fuse protection type none
fuse protection type in the feeder Required: 3-pole connected miniature circuit breaker 10 ... 16 A characteristic C or circuit breaker 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10 (UL 489-listed, DIVQ)
output
voltage curve at output Controlled, isolated DC voltage
output voltage at DC rated value 24 V
output voltage  
● at output 1 at DC rated value 24 V
   
output voltage adjustable Yes; via potentiometer
adjustable output voltage 24 ... 28 V; max. 960 W
relative overall tolerance of the voltage 3 %
relative control precision of the output voltage  
● on slow fluctuation of input voltage 1 %
● on slow fluctuation of ohm loading 2 %
residual ripple  
● maximum 150 mV
voltage peak  
● maximum 240 mV
display version for normal operation Green LED for 24 V OK
type of signal at output Relay contact (NO contact, rating 60 V DC/ 0.3 A) for "24 V OK"
behavior of the output voltage when switching on No overshoot of Vout (soft start)
response delay maximum 1.5 s
voltage increase time of the output voltage  
● typical 15 ms
● maximum 500 ms
output current  
● rated value 40 A
● rated range 0 ... 40 A; 48 A up to +45°C; +60 ... +70 °C: Derating 3%/K
   
supplied active power typical 960 W
short-term overload current  
● on short-circuiting during the start-up typical 65 A
● at short-circuit during operation typical 65 A
duration of overloading capability for excess current  
● on short-circuiting during the start-up 100 ms
● at short-circuit during operation 100 ms
bridging of equipment Yes
number of parallel-switched equipment resources for increasing the power 2
efficiency
efficiency in percent 91.5 %
power loss [W]  
● at rated output voltage for rated value of the output current typical 89 W
closed-loop control
relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical 3 %
relative control precision of the output voltage load step of resistive load 50/100/50 % typical 1.5 %
setting time  
● load step 50 to 100% typical 1 ms
● load step 100 to 50% typical 1 ms
relative control precision of the output voltage at load step of resistive load 10/90/10 % typical 3 %
setting time  
● load step 10 to 90% typical 1 ms
● load step 90 to 10% typical 1 ms
● maximum 10 ms
protection and monitoring
design of the overvoltage protection protection against overvoltage in case of internal fault Vout < 35 V
property of the output short-circuit proof Yes
design of short-circuit protection Electronic shutdown, automatic restart
● typical 50 A
overcurrent overload capability  
● in normal operation overload capability 150 % Iout rated up to 5 s/min
enduring short circuit current RMS value  
● maximum 14 A
safety
galvanic isolation between input and output Yes
galvanic isolation Safety extra-low output voltage Vout acc. to EN 60950-1 and EN 50178, transformer acc. to EN 61558-2-16
operating resource protection class Class I
protection class IP IP20
EMC
standard  
● for emitted interference EN 55022 Class B
● for mains harmonics limitation EN 61000-3-2
● for interference immunity EN 61000-6-2
standards, specifications, approvals
certificate of suitability  
● CE marking Yes
● UL approval Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)
● CSA approval Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)
● UKCA marking Yes
● EAC approval Yes
● NEC Class 2 No
type of certification  
● BIS Yes; R-41183539
● CB-certificate Yes
MTBF at 40 °C 500 000 h
standards, specifications, approvals hazardous environments
certificate of suitability  
● IECEx No
● ATEX No
● ULhazloc approval No
● cCSAus, Class 1, Division 2 No
● FM registration No
standards, specifications, approvals marine classification
shipbuilding approval Yes
Marine classification association  
● American Bureau of Shipping Europe Ltd. (ABS) Yes
● French marine classification society (BV) No
● Det Norske Veritas (DNV) Yes
● Lloyds Register of Shipping (LRS) No
standards, specifications, approvals Environmental Product Declaration
Environmental Product Declaration Yes
global warming potential [CO2 eq]  
● total 2 847 kg
● during manufacturing 61.2 kg
● during operation 2 783.6 kg
● after end of life 0.92 kg
ambient conditions
ambient temperature  
● during operation -25 ... +70 °C; with natural convection
● during transport -40 ... +85 °C
● during storage -40 ... +85 °C
environmental category according to IEC 60721 Climate class 3K3, 5 ... 95% no condensation
connection method
type of electrical connection screw terminal
● at input L1, L2, L3, PE: 1 screw terminal each for 0.5 ... 4 mm² single-core/finely stranded
● at output +, -: 2 screw terminals each for 0.5 ... 10 mm²
● for auxiliary contacts 13, 14 (alarm signal): 1 screw terminal each for 0.05 ... 2.5 mm²
mechanical data
width × height × depth of the enclosure 145 × 145 × 150 mm
installation width × mounting height 145 mm × 225 mm
required spacing  
● top 40 mm
● bottom 40 mm
● left 0 mm
● right 0 mm
fastening method Snaps onto DIN rail EN 60715 35x15
● DIN-rail mounting Yes
● S7 rail mounting No
● wall mounting No
housing can be lined up Yes
net weight 3.1 kg
accessories
electrical accessories Redundancy module, buffer module, selectivity module, DC UPS
mechanical accessories Device identification label 20 mm × 7 mm, pale turquoise 3RT1900-1SB20

More detail about Green Energy Automation Sdn Bhd
Green Energy Automation Sdn Bhd
Green Energy Automation Sdn Bhd Industrial Process Automation & Control Systems Johor, PLC System Integration Services Malaysia | Green Energy Automation Sdn Bhd
Contact Us flagMalaysia