SIMATIC S7-1500, digital output module DQ 16x 230V AC/2A ST; relay 16 channels in groups of 2; 4 A per group; switching cycle counter for integrated relay

SIMATIC S7-1500, digital output module DQ 16x 230V AC/2A ST; relay 16 channels in groups of 2; 4 A per group; switching cycle counter for integrated relay

Category: SIEMENS Simatic Control Systems Available
For more information, visit our official website at geasb.com

Description

General information
Product type designation DQ 16x 230 V AC/2 A ST (relay)
HW functional status FS01
Firmware version V1.1.0
● FW update possible Yes
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode No
● Prioritized startup Yes
Engineering with
● STEP 7 TIA Portal configurable/integrated from version V13 SP1 / -
● STEP 7 configurable/integrated from version V5.5 SP3 / -
● PROFIBUS from GSD version/GSD revision V1.0 / V5.1
● PROFINET from GSD version/GSD revision V2.3 / -
Operating mode
● DQ Yes
● DQ with energy-saving function No
● PWM No
● Oversampling No
● MSO Yes
● Integrated operating cycle counter Yes; FW V1.1.0 or higher
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption, max. 185 mA
output voltage / header
Rated value (AC) 230 V; 24 V DC to 120 V DC / 24 V AC to 230 V AC
Power
Power consumption from the backplane bus 0.8 W
Power loss
Power loss, typ. 5 W
Digital outputs
Type of digital output Relays
Number of digital outputs 16
Current-sinking Yes
Current-sourcing Yes
Digital outputs, parameterizable Yes
Short-circuit protection No
Controlling a digital input Yes
Size of motor starters according to NEMA, max. 5
Switching capacity of the outputs
● on lamp load, max. 50 W (230 V AC), 5 W (24 V DC)
Output current
● for signal "1" rated value 2 A
● for signal "1" permissible range, min. 10 mA; 10 V
● for signal "1" permissible range, max. 2 A; thermal continuous current
● for signal "0" residual current, max. 0 A
Parallel switching of two outputs
● for logic links Yes
● for uprating No
● for redundant control of a load Yes
Switching frequency
● with resistive load, max. 1 Hz
● with inductive load, max. 0.5 Hz
● on lamp load, max. 1 Hz
Total current of the outputs
● Current per channel, max. 2 A; see additional description in the manual
● Current per group, max. 4 A; see additional description in the manual
● Current per module, max. 32 A; see additional description in the manual
Relay outputs
● Number of relay outputs 16
● Rated supply voltage of relay coil L+ (DC) 24 V
● Current consumption of relays (coil current of all relays), typ. 150 mA
● external protection for relay outputs Miniature circuit breaker B10 / B16
● Contact connection (internal) No
● Number of operating cycles, max. see additional description in the manual
Switching capacity of contacts
— with inductive load, max. 2 A; see additional description in the manual
— with resistive load, max. 2 A; see additional description in the manual
Cable length
● shielded, max. 1 000 m
● unshielded, max. 600 m
Interrupts/diagnostics/status information
Substitute values connectable Yes
Alarms
● Diagnostic alarm Yes
● Maintenance interrupt Yes
Diagnoses
● Monitoring the supply voltage Yes
● Wire-break No
● Short-circuit No
Diagnostics indication LED
● RUN LED Yes; green LED
● ERROR LED Yes; red LED
● MAINT LED Yes; Yellow LED
● Monitoring of the supply voltage (PWR-LED) Yes; green LED
● Channel status display Yes; green LED
● for channel diagnostics No
● for module diagnostics Yes; red LED
Potential separation
Potential separation channels
● between the channels No
● between the channels, in groups of 2
● between the channels and backplane bus Yes
● Between the channels and load voltage L+ Yes
Permissible potential difference
between different circuits 250 V AC between the channels and the supply voltage L+; 250 V AC between the channels and the backplane bus; 500 V AC between the channels
Isolation
Isolation tested with Between channels: 3 100 V DC; between channels backplane bus: 3 100 V DC; between L+ and backplane bus: 707 V DC (type test)
Standards, approvals, certificates
Siemens Eco Profile (SEP) Siemens EcoTech
Suitable for safety functions No
Suitable for safety-related tripping of standard modules Yes; From FS02
Ecological footprint
● environmental product declaration Yes
Global warming potential
— global warming potential, (total) [CO2 eq] 43.8 kg
— global warming potential, (during production) [CO2 eq] 9.5 kg
— global warming potential, (during operation) [CO2 eq] 34.5 kg
— global warming potential, (after end of life cycle) [CO2 eq] -0.231 kg
Highest safety class achievable for safety-related tripping of standard modules
● Performance level according to ISO 13849-1 PL c
● Category according to ISO 13849-1 Cat. 2
● SIL acc. to IEC 62061 SIL 1
● remark on safety-oriented shutdown https://support.industry.siemens.com/cs/de/en/view/39198632
product functions / security / header
signed firmware update No
data integrity No
Ambient conditions
Ambient temperature during operation
● horizontal installation, min. -25 °C; From FS02
● horizontal installation, max. 60 °C
● vertical installation, min. -25 °C; From FS02
● vertical installation, max. 40 °C
Dimensions
Width 35 mm
Height 147 mm
Depth 129 mm
Weights
Weight, approx. 350 g