Feature | Specification |
---|---|
Sensing Element | Pt1000 (platinum resistance) |
Probe Length | 400 /mm (16″) bendable copper/polyolefin |
Temperature Range | –50 /°C to +50 /°C (–58 /°F to +122 /°F) |
Operating Voltage | 13.5–35 /V /DC |
Output Signal | 4–20 /mA (loop-powered, 2-wire) |
Accuracy | ±0.9 /K (–50…+50 /°C) |
Time Constant | ~30 /s at air velocity of 2 /m/s |
Housing/IP Rating | Plastic enclosure, IP54 |
Power Consumption | < /1 /VA |
Dimensions | Housing ~88×80×39 /mm, probe 400 /mm |
Protection Class | Class /III (low voltage) |