Display: 4-digit 7-segment LED
Control Methods: ON/OFF, P, PI, PD, PID
Input Types:
Thermocouples: K, J, E, T, B, R, S, N, C, G, L, U, Platinel II
RTD: DPt100Ω, DPt50Ω, JPt100Ω, Cu100Ω, Cu50Ω, Nickel 120Ω
Analog: 0–100mV, 0–5V, 1–5V, 0–10V, 0–20mA, 4–20mA
Sampling Cycle: 50ms
Control Output: Relay (250VAC, 3A)
Optional Outputs: Alarm 1, DC 4–20mA transmission
Power Supply: 100–240VAC, 50/60Hz
Protection Rating: IP65 (front panel)
Display Accuracy:
RTD/Thermocouple: ±0.3% or ±1°C (whichever is greater) at room temperature (23°C ±5°C); ±0.5% or ±2°C outside room temperature
Analog: ±0.3% F.S. ±1 digit at room temperature; ±0.5% F.S. ±1 digit outside room temperature
CT Input: ±5% F.S. ±1 digit
Hysteresis: Adjustable from 1 to 100°C (0.1 to 100.0°C)
Proportional Band: 0.1 to 999.9°C (0.1 to 999.9%)
Integral Time: 0 to 9999 seconds
Derivative Time: 0 to 9999 seconds
Control Period: 0.1 to 120.0 seconds for relay/SSR drive output; 1.0 to 120.0 seconds for current output or SSR drive output
Manual Reset: 0.0 to 100.0%
Ambient Temperature: Operating: -10 to 50°C; Storage: -20 to 60°C
Ambient Humidity: 35 to 85% RH (non-condensing)
Insulation Type: Double or reinforced insulation; dielectric strength between measuring input and power part: 2kV
Weight: Approximately 150g (unit only)