HT11 Series Tower Online UPS 6-20kVA (220V/230V/240V)

HT11 Series Tower Online UPS 6-20kVA (220V/230V/240V)

Category: Single-Phase UPS Available
For more information, visit our official website at pstech.my

Description

HT11 Series Tower Online UPS 6–20kVA (220V/230V/240V)

Single Phase Double Conversion High Performance

The HT11 Series Tower Online UPS offers reliable, uninterrupted power for critical applications. Available in both standard models with built-in batteries and long backup models, this single-phase UPS combines compact design with high power density. Featuring advanced DSP-controlled double conversion technology, it is an ideal solution for computers, telecom systems, and other sensitive electronics. Available capacities include 6kVA, 10kVA, 15kVA, and 20kVA.


Key Features:


Perfect for mission-critical environments that demand clean and continuous power, the HT11 Series delivers performance, reliability, and flexibility—all in a compact tower form.

Specifications

  HT1106XS HT1106XL HT1110XS HT1110XL
INPUT  
Cold Start YES
Default output frequency will be 50Hz or settable
Acceptable Input Voltage 110VAC~288VAC
  100% load@>176VAC
90% load@>154VAC
75% load@>132VAC
50% load@>110VAC
Phase Single phase in,single phase out
Transfer Voltage Range   220VAC/230VAC/240VAC(PF=1)
    -Line low transfer 110VAC
    -Line low recovery 121VAC
    -Line high transfer 288VAC
    -Line high recovery 281VAC
Input Current  
    -Rating(nominal input voltage) 30A/220V 34A/220V 49A/220V 53A/220V
Input Power Factor 0.99
Input current distortion <4%
Input Frequency Range 40~70Hz
OUTPUT  
Frequency adaptable Settable
Power  
    -Power 6KVA 10KVA
    -Power(kW)  6KW 10KW
Output Voltage  
    -Waveform(Bat. Mode) Pure Sine Wave
    -Nominal voltage 220VAC/230VAC/240VAC
    -Voltage regulation ± 1 %
    -Voltage distortion 1% THD, linear load        
 5% THD, non linear load
Output Frequency  
    -Synchronization range 50/60 HZ±5Hz default, settable
    -Battery mode (50±0.1) Hz default
Transfer Time  
    -Line mode to battery mode 0ms
    -Inverter to bypass 0ms
Efficiency  
    -Line mode with battery full charged 95%MAX
    -ECO mode 98.0%
Noise(1m away)  <58dB
Overload Capability(Inverter) 105% to 110% : Transfer to bypass after 10 mins.
111% to 125% : Transfer to bypass after 1 mins.
126% to 150%: Transfer to bypass after 30s
Overload Capability (Bypass Mode) less than 125%: long time running
 126% to 130% :Shutdown in 5 mins
 131% to 150% :Shutdown in 1 mins
> 150%  :Shutdown in 200 ms
Crest Ratio 3:1
BATTERY  
Rating/Type 12VDC/7Ah Depend on the capacity of external batteries 12VDC/9Ah Depend on the capacity of external batteries
Quantity 16PCS default, 20PCS settable 16-20PCS settable 16PCS default, 20PCS settable 16-20PCS settable
DC Voltage 192VDC default, settable
Back-up Time 4.5mins @80%load Depend on the capacity of external batteries 2.5mins @80%load Depend on the capacity of external batteries
Charger  
    -Charging current (max) 1A, settable 5A max,settable 1A,settable 5A max,settable
    -Float Charging Voltage 2.25V/cell default, setttable via software
    -Boost Charging Voltage 2.25V/cell default, setttable via software
    -Charging time 8h recharge to 90% Depend on the capacity of external batteries 8h recharge to 90% Depend on the capacity of external batteries
Leakage current <3mA
Indicator & Alarm  
    -Display LED+LCD
Inteface  
    -Smart RS232 Standard Cable support INVT Power Monitor Software
    -EPO NC
    -RS485(option) Installed in the intelligent slot
    -SNMP(option) Power Managment from SNMP Manager and Web Browser
Option  
    -Intelligent Kits DB9 port, dry contact
    -parallel 4 units paralleled
    -Super charger (12A) digitally controlled, 4-steps charge, settable,@PF0.9
    -USB B-type USB port
    -SNMP Kits Pluggable type
Working Enviroment  
Mechanical  
    -W%sD%sH (mm) 190*426*705  190*426*336 190*485*705 190*485*336
    -Net Weight (KG) 56 14 60 16
    -Package Weight (KG) 61 15 70 17
    -Rack / Tower Tower
Color Black default
 
  HT1115XL   HT1120XL
INPUT  
Cold Start YES
Default output frequency will be 50Hz or settable
Acceptable Input Voltage 110VAC~288VAC
  100% load@>176VAC
90% load@>154VAC
75% load@>132VAC
50% load@>110VAC
Phase Single phase in,single phase out
Transfer Voltage Range    220/230/240VAC
    -Line low transfer 110VAC
    -Line low recovery 121VAC
    -Line high transfer 288VAC
    -Line high recovery 281VAC
Input Current  
    -Rating(nominal input voltage) 25A/380V 33A/380V
    -Input Power Factor 0.99
    -Input current distortion 4%
    -Input Frequency Range 40~70Hz
OUTPUT  
Frequency adaptable Settable
Power  
    -Power 15KVA 20KVA
    -Power(kW)  15KW 20KW
Output Voltage  
    -Waveform(Bat. Mode) Pure Sine Wave
    -Nominal voltage L-N 220VAC/230VAC/240VAC,  200VAC/208VAC(PF=0.9)
    -Voltage regulation ± 1 %
    -Voltage distortion 1% THD, linear load        
5% THD, non linear load
Output Frequency  
    -Synchronization range ±5Hz default, settable
    -Battery mode (50±0.1) Hz default
Transfer Time  
    -Line mode to battery mode 0ms
    -Inverter to bypass 0ms
Efficiency  
    -Line mode with battery full charged 94%@100% load, 94.5%@70% load
    -ECO mode 98.0%
Noise(1m away)  <62dB
Overload Capability(Inverter) 105% to 110% : Transfer to bypass after 10 mins.
111% to 125% : Transfer to bypass after 1 mins.
126% to 150%: Transfer to bypass after 30s
Overload Capability (Bypass Mode) less than 125%: long time running
 126% to 130% :Shutdown in 5 mins
 131% to 150% :Shutdown in 1 mins
> 150%  :Shutdown in 200 ms
BATTERY  
Quantity 16-20PCS settable
DC Voltage 192VDC default, settable
Charger  
    -Charging current (max) 5A max,settable
    -Float Charging Voltage 2.25V/cell default, setttable via software
    -Boost Charging Voltage 2.25V/cell default, setttable via software
Indicator & Alarm  
    -Display LED+LCD
Inteface  
    -Smart RS232 Standard Cable support INVT Power Monitor Software
    -EPO NC, NO settable, forbidden default
    -RS485(option) Installed in the intelligent slot
    -SNMP(option) Power Managment from SNMP Manager and Web Browser
Option  
    -Intelligent dry contact DB9 port or terminal
    -parallel 4 units paralleled
    -Super charger (12A) digitally controlled, 4-steps charge, settable
    -USB B-type USB port
    -SNMP Kits Pluggable type
Working Enviroment  
    -storage  -40~70
    -working 0~40, huminity 95% non condesation, attitude<1500m (@full load)
Mechanical  
    -W%sD%sH (mm) 190*485*480
    -Net Weight (KG) 30
    -Package Weight (KG) 33
    -Rack / Tower Tower