96% efficiency with ECO-mode optimization.
PF >0.99 and THDi <3% with full-load capacity.
50%+ longer battery life vs. traditional solutions.
30% smaller footprint than competitors, with modular subsystems for <15-minute component swaps.
High power density design with full front maintenance and support for top and bottom cable entry methods, saving installation space.
| MODEL | HTD33120 | HTD33160 | HTD33200 |
| System Capacity | 120kVA | 160kVA | 200kVA |
| Power Module Capacity | 60kVA/60kW | 80kVA/80kW | 100kVA/100kW |
| Main Input | |||
| Grid System | 3P+N+PE | ||
| Rated Input Voltage | 380/400/415VAC (line-line) | ||
| Rated Frequency | 50/60Hz | ||
| Input Voltage Range | 323~478Vac (line-line), full load @ 30~40℃ 323~138Vac (line-line), load decrease linearly from 100% load to 30% load @ 30~40℃ |
||
| Input Frequency Range | 40Hz~70Hz | ||
| Input Power Factor | >0.99 | ||
| Input Current THDi | <3% (full Linear load) | ||
| Bypass | |||
| Rated Bypass Voltage | 380/400/415VAC (line-line) | ||
| Rated Bypass Frequency | 50/60Hz | ||
| Bypass Voltage Range | Settable, default -20%~+15% Upper limited: +10%, +15%, +20%, +25% Lower limited: -10%, -15%, -20%, -30%, -40% |
||
| Bypass Frequency Range | Settable, ±1Hz, ±3Hz, ±5Hz | ||
| Bypass Overload | 125%, long term operation 125%~130%, 10 minutes 130%~150%, 1 minute >150%, 300ms |
||
| Output | |||
| Rated Voltage | 380/400/415VAC (line-line) | ||
| Rated Frequency | 50/60Hz | ||
| Output Power Factor | 1 | ||
| Voltage Precision | ±1% | ||
| Transient Response | <5% (0% - 100% -0% step load) | ||
| Transient Recovery | < 40ms (0% - 100% -0% step load) | ||
| Output Voltage THDu | <1%, linear load <5%, non-linear load (IEC/EN62040-3) |
||
| Inverter Overload | <110%, 60 mins 110%~125%, 10mins 125%~150%, 1min >150%, 200ms |
||
| Frequency Regulation | 50/60Hz±0.1% | ||
| Synchronized Range | Settable, ±0.5Hz~±5Hz, default ±3Hz | ||
| Synchronized Slew Rate | Settable, 0.5Hz/S~3Hz/S, default 0.5Hz/S | ||
| Battery and Charger | |||
| Battery Rated Voltage | ±240VDC 30pcs derated 0.7 32~34pcs derated 0.8 36~38pcs derated 0.9 40~48pcs non-derating |
||
| Charger Voltage Precision | 1% | ||
| Charger Power | max=15% * Output active power | ||
| Effiency | |||
| Normal Operation | >96% | ||
| Battery Operation | >95% | ||
| Power Module Weight (kg) | 44.8 | 51.2 | 53.5 |
| System | |||
| Display | LCD + LED + Color touch screen | ||
| Interface | RS485, USB, CAN, Programmable dry contact, 2 intelligent card slots, 1 expandable dry contact slot | ||
| Option | SNMP card, AS400, Parallel kit, Lightning protection components, Copper bar, LBS, SMS alarm, RS485 expansion card |
||
| Environment | |||
| Operation Temperature | 0~40 ℃ | ||
| Storage Temperature | -40~70 ℃ | ||
| Relative Humidity | 0 ~ 95% Non condensing | ||
| Noise (1 meter) | 75dB @ 100% load, 70dB @ 45% load | ||
| Altitude | <1000m, Load derated 1% per 100m From 1000~2000m | ||
| Physical | |||
| Cabinet Dimension (W*D*H, mm) |
480*1100*1200 | ||
| Cabinet Weight (kg) | 78.8 | ||
| Power Module Dimension (W*D*H, mm) |
440*795*174 | ||
| Power Module Weight (kg) | 44.8 | 51.2 | 53.5 |