Product Overview
Filter media made of synthetic fibers, offering low resistance to airflow and high dust-holding capacity. Ideal for pre-filtration in air ventilation and air-conditioning (HVAC) systems.
Technical Specification
| Technical Specification | Model: GRC | ||||
| 150 | 200 Black | 250 Blue + White | 350 | ||
| Thickness (approx) | 12mm | 5mm | 18-20mm | 20-22mm | |
| Standard Length | 20m | 20m | 20m | 20m | |
| Standard Width | 2m | 2m | 2m | 2m | |
| Weight | 150g/m2 | 125g/m2 | 250g/m2 | 380g/m2 | |
| Roll Diameter | 0.3m | 0.3m | 0.6m | 0.8m | |
| Media Colour | White | Black | Blue/White | White | |
| Air Permeability | 4500l/m2 | 4500l/m2 | 4300l/m2 | 1500l/m2 | |
| Face Dimensions (mm) | 610 x 610 | 610 x 610 | 610 x 610 | 610 x 610 | |
| Arrestance | 75-80% | 75-80% | 80-85% | 90-92% | |
| Air Flow Rate | 0.56m3/s | 0.56m3/s | 0.8m3/s | 0.25m3/s | |
| Initial / Final Resistance (Pa) | 17 / 130 | 17 / 130 | 26 / 200 | 42 / 250 | |
| Dust Holding Capacity | 140g | 140g | 175g | 250g | |
| Flame Behaviour / DIN 53438 | F1/F2 | F1/F2 | F1/F2 | F1/F2 | |
| EN779 Classification | G2 | G2 | G3 | G4 | |
| Max Operation Temp | 100 oC | 100 oC | 100 oC | 100 oC |