KEY FEATURES:
HIGH YIELD

| SG110CX-P2-CN Inverter Specifications | |
|---|---|
| Type designation | SG110CX-P2-CN | 
| Input (DC) | |
| Max. PV input voltage | 1100V | 
| Min. operating PV voltage / Start-up input voltage | 180V / 200V | 
| Rated PV input voltage | 640V | 
| MPPT voltage range | 180~1000V | 
| No. of independent MPP inputs | 9 | 
| No. of PV strings per MPPT | 2 | 
| Max. PV input current per String | 15A | 
| Max. PV input current | 270A (9×30A) | 
| Max. PV input current per Input Connector | 30A | 
| Max. DC short-circuit current | 360A (9×40A) | 
| Output (AC) | |
| Rated AC output power | 110kW | 
| Max. AC output power | 121kW | 
| Max. AC output apparent power | 121kVA | 
| Max. AC output current | 183.3A | 
| Rated AC voltage | 3 / N / PE, 230/400V | 
| AC voltage range | 320~480V | 
| Rated grid frequency / Grid frequency range | 50Hz / 45~55Hz 60Hz / 55~65Hz | 
| Harmonic (THD) | < 3% (at rated power) | 
| Power factor at nominal power | > 0.99 (at rated power) | 
| Adjustable power factor | 0.8 leading – 0.8 lagging | 
| Feed-in phases / AC connection | 3 / 3 | 
| Efficiency | |
| Max. efficiency | 98.60% | 
| European efficiency | 98.00% | 
| Protection and Function | |
| DC reverse polarity protection | Yes | 
| AC short-circuit protection | Yes | 
| Leakage current protection | Yes | 
| Grid monitoring | Yes | 
| DC switch | Yes | 
| PV string monitoring | Yes | 
| Anti-Islanding protection | Yes | 
| Surge protection | DC Type II / AC Type II | 
| General Data | |
| Dimensions (W*H*D) | 1019*793*360mm | 
| Weight | 82kg | 
| Topology | Transformerless | 
| Degree of protection | IP66 | 
| Night power consumption | ≤ 4W | 
| Operating ambient temperature range | -30~+60℃ | 
| Allowable relative humidity range | 0~100% | 
| Cooling method | Smart forced air cooling | 
| Max. operating altitude | 4000m (>3000m derating) | 
| Display | LED, Bluetooth+APP | 
| Communication | RS485 / Optional: WLAN, Ethernet | 
| DC connection type | MC4 | 
| AC connection type | OT / DT terminal (From 70 ~ 240 mm²) | 
| Compliance with Standard | NB/T 32004-2018; GB/T 37408-2019 | 
| Grid Support | LVRT, HVRT, Anti-Islanding, active & reactive power control, and power ramp rate control |