Description
QEED Isolated Signal Converter
QA-VI Current / Voltage Converter
The QEED QA-VI is a 4-way galvanically isolated voltage or current signal converter with analogue input, programmable analogue output, relay alarm output and RS485 Modbus RTU communication. It is suitable for industrial signal conversion, monitoring, alarm and data acquisition applications.
The module behaves as a Modbus RTU slave device with 1 analogue input, 1 analogue output and 1 digital relay output. It can also perform datalogging through USB On-The-Go using a pen drive, with an integrated real-time clock for timestamped data storage.
Input
Voltage or current analogue input
Outputs
Analogue, relay and RS485 Modbus
Isolation
4-way galvanic isolation
Datalogging
USB pen drive logging with RTC
Overview
QA-VI is used when a field voltage or current signal must be isolated, converted, retransmitted, monitored and made available through Modbus RTU. It can convert analogue signals into programmable voltage or current output while also providing a relay alarm and RS485 communication.
The 17.5mm DIN rail format makes it suitable for control panels, machine panels, energy monitoring systems, process instrumentation, BMS, EMS, SCADA, PLC and industrial IoT applications.
Positioning: 4-way isolated current / voltage signal converter with programmable analogue output, alarm relay, RS485 Modbus and USB datalogging.
Key Features
Voltage or Current Input
Accepts programmable voltage input up to 10Vdc or current input up to 20mA.
Programmable Analogue Output
Provides configurable voltage or current output for retransmission to PLC, BMS or monitoring systems.
Relay Alarm Output
5A SPDT relay contact can be configured as an alarm or threshold output.
RS485 Modbus RTU
Communicates as a Modbus RTU slave for SCADA, EMS, BMS, PLC and gateway integration.
USB Datalogger
Logs data to USB pen drive through USB On-The-Go, with integrated real-time clock.
USB / RS485 Configuration
Configured using free FACILE QA-VI software via USB or RS485, with DIP switch support for address and baud rate.
Input and Output Functions
| Function |
Specification |
Purpose |
| Voltage Input |
Programmable up to 10Vdc, input impedance 100kΩ, 1mV resolution |
Signal conversion from voltage transducers and process instruments |
| Current Input |
Programmable up to 20mA, input impedance 20Ω, max resolution 2 礎 |
Signal conversion from 0/4 20mA field instruments |
| Current Output |
0 20mA programmable, max load resistance 600Ω |
Retransmission to PLC, BMS, EMS, controller or recorder |
| Voltage Output |
0 10V programmable, minimum load resistance 2kΩ |
Retransmission to analogue input systems |
| Contact Alarm |
5A / 230Vac SPDT relay, programmable by FACILE QA-VI |
Local alarm, threshold output or control signal |
| RS485 Modbus |
RS485 Modbus RTU slave on terminals or optional base adapter |
Digital integration to SCADA, EMS, BMS, PLC and IoT gateways |
4-Way Isolation
QA-VI is designed with 4-way galvanic isolation between the input, analogue / digital outputs, RS485 / USB communication and power supply. This helps reduce signal interference and protects systems where different parts of the installation may have different electrical references.
Isolation paths: Input, analogue and digital output, RS485 / USB communication and power supply are galvanically isolated at 1.5kV.
Datalogging Function
QA-VI includes datalogging using a USB On-The-Go port and pen drive memory. The integrated real-time clock enables timestamped data storage. Logged data can be downloaded in Excel-importable files for analysis, reporting or troubleshooting.
- USB pen drive data logging
- Integrated RTC real-time clock
- Configuration of logging parameters through FACILE QA-VI
- Storage data export in Excel-importable format
- Useful for temporary measurement, commissioning and fault investigation
Technical Specifications
| Parameter |
Specification |
| Power Supply |
10 to 40Vdc or 20 to 28Vac, 50/60Hz |
| Input |
Voltage up to 10Vdc or current up to 20mA, programmable |
| Retransmission Output |
Isolated analogue output, programmable voltage or impressed current; active or passive output supply |
| Sensor Power Supply |
13Vdc, 30mA max |
| Absorption |
Maximum 20VA |
| Protection Index |
IP20 |
| Accuracy |
0.1% F.S. |
| Resolution |
16-bit |
| Rejection |
50 60Hz |
| Thermal Stability at 25°C |
<100ppm / °C |
| Working Temperature |
-15°C to +65°C |
| Storage Temperature |
-40°C to +85°C |
| Isolation |
Input, analogue / digital output, RS485 / USB and power supply isolated at 1.5kV |
| Humidity |
10% to 90%, non-condensing |
| Altitude |
Up to 2000m a.s.l. |
| Mounting |
DIN rail mounting with removable terminals; optional base connection for RS485 bus and supply |
| Connections |
Removable 5.08mm terminals |
| CE Standards |
EN61000-6-4:2006 + A1:2011; EN61000-6-2:2005; EN61010-1:2010 |
| Dimensions |
17.5 x 100 x 112mm, terminals excluded |
| Datalogger |
Non-volatile memory, USB On-The-Go logging with pen drive, Excel-importable file output, integrated RTC |
| Configuration |
FACILE QA-VI software via USB or RS485; DIP switch for Modbus address and baud rate |
Typical Applications
Signal Isolation
Isolate and retransmit voltage or current signals between instruments and control systems.
PLC / SCADA Integration
Convert analogue field signals into PLC analogue input, Modbus RTU data and alarm output.
BMS and EMS Panels
Use in building and energy management systems for signal conversion and alarm monitoring.
Temporary Logging
Use USB logging for commissioning, troubleshooting, trend capture and site investigations.
Process Monitoring
Convert sensor or transmitter signals into standard output formats for industrial monitoring.
IoTWatt 4.0
Can be integrated through Modbus RTU or compatible input modules into IoTWatt 4.0 systems.
Configuration
QA-VI can be configured using the free FACILE QA-VI software through USB or RS485. The software allows configuration of conversion parameters, span, zero, alarm contact, logging settings and Modbus communication parameters.
- Configure voltage or current input range
- Configure analogue output range and scaling
- Set span and zero
- Set relay alarm threshold and behaviour
- Configure Modbus address and baud rate
- Configure USB datalogging interval and data storage
- Use DIP switches for basic Modbus address and baud rate settings
Commissioning note: Confirm input type, output type, scaling, relay alarm logic and Modbus settings before connecting the module into a live control or monitoring system.
System Integration
QA-VI is suitable for converting and isolating field signals before they are connected to PLC, SCADA, BMS, EMS, Modbus gateway, data logger or IoTWatt 4.0. The combination of analogue output, relay output, RS485 Modbus and USB datalogging makes it useful for both permanent and temporary measurement applications.
- Use analogue output for direct PLC or controller connection
- Use relay output for alarm or threshold indication
- Use RS485 Modbus RTU for digital system integration
- Use USB datalogging for commissioning and troubleshooting
- Use optional base connection for cleaner multi-module panel wiring
QA-VI Supply and Integration
Saturn Pyro supports QEED QA-VI current / voltage converters for signal isolation, analogue retransmission, alarm output, RS485 Modbus integration, USB datalogging, PLC, SCADA, BMS, EMS and IoTWatt 4.0 projects in Malaysia.
Enquire Now